PREL201701082
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Final Inspection | Pending | |||
Electrical Rough-in Inspection | Partial Pass | 3/16/2017 (8:00 - 10:00) | 3/16/2017 | 03/16/2017 |
Corrections:
Miscellaneous/Other
Carried Forward
03/16/2017
Water feature requires UL listing of water pumps and LED lighting per NEC 410.
Elec RI of column 4-plex for water feature.
|
||||
Electrical Rough-in Inspection | Not Ready | 3/30/2017 (8:00 - 10:00) | 3/30/2017 | 03/30/2017 |
Corrections:
Miscellaneous/Other
Carried Forward
03/30/2017
Water feature requires UL listing of water pumps and LED lighting per NEC 410.
|
||||
Electrical Rough-in Inspection | Partial Pass | 4/10/2017 (8:00 - 10:00) | 4/10/2017 | 04/10/2017 |
Corrections:
Miscellaneous/Other
Carried Forward
04/10/2017
Water feature requires UL listing of water pumps and LED lighting per NEC 410.
|
||||
Miscellaneous/Other
Carried Forward
04/10/2017
RI - walls in air museum and dining room tv outlet.
|
||||
Electrical Final Inspection | Partial Pass | 5/19/2017 (10:00 - 12:00) | 5/19/2017 | 05/19/2017 |
Corrections:
Miscellaneous/Other
Carried Forward
05/19/2017
Connect canopy heater.
Final - banquet room only.
|
||||
Electrical Rough-in Inspection | Partial Pass | 7/25/2017 (12:30 - 2:30) | 7/26/2017 | 07/26/2017 |
Corrections:
Miscellaneous/Other
Outstanding
04/10/2017
Water feature requires UL listing of water pumps and LED lighting per NEC 410.
|
||||
Miscellaneous/Other
Outstanding
04/10/2017
RI - walls in air museum and dining room tv outlet.
|
||||
Miscellaneous/Other
Comment Only
07/26/2017
RI - banquet room bar walls and ceiling.
|
||||
Electrical Final Inspection | Failed | 10/5/2017 (12:30 - 2:30) | 10/5/2017 | 10/05/2017 |
Corrections:
Miscellaneous/Other
Carried Forward
10/05/2017
Connect canopy heater.
Final - banquet room only.
|
||||
Miscellaneous/Other
Carried Forward
10/05/2017
GFI-protect back wall counter outlets.
Replace cooler GFI outlets and install GFI breakers.
Open j-boxes above ceiling.
Dead outlets - S. side cabinets.
Install breaker lock-off for dishwasher and label circuit info on DW.
|
||||
Electrical Final Inspection | Failed | 10/6/2017 (2:30 - 3:30) | 10/6/2017 | 10/06/2017 |
Corrections:
Miscellaneous/Other
Carried Forward
10/06/2017
Connect canopy heater.
Final - banquet room only.
|
||||
Miscellaneous/Other
Carried Forward
10/06/2017
GFI-protect back wall counter outlets.
Replace cooler GFI outlets and install GFI breakers.
Open j-boxes above ceiling.
Dead outlets - S. side cabinets.
Install breaker lock-off for dishwasher and label circuit info on DW.
|
||||
Miscellaneous/Other
Carried Forward
10/06/2017
Repalce gfci outlets behind pizza coolers and fridge and install gfci breakers.
Install exit lighting per plan and code.
|
||||
Electrical Final Inspection | Partial Pass | 10/10/2017 (8:00 - 10:00) | 10/10/2017 | 10/10/2017 |
Corrections:
Miscellaneous/Other
Outstanding
10/06/2017
Connect canopy heater.
Final - banquet room only.
|
||||
Miscellaneous/Other
Outstanding
10/06/2017
GFI-protect back wall counter outlets.
Replace cooler GFI outlets and install GFI breakers.
Open j-boxes above ceiling.
Dead outlets - S. side cabinets.
Install breaker lock-off for dishwasher and label circuit info on DW.
|
||||
Miscellaneous/Other
Outstanding
10/06/2017
Repalce gfci outlets behind pizza coolers and fridge and install gfci breakers.
Install exit lighting per plan and code.
|
||||
Miscellaneous/Other
Outstanding
10/10/2017
Sign and island table electrical to complete.
|