Permit Application Status

PREL201704144


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL201704144
Electrical
Finaled
PHD PROPERTIES LLC
Alteration/Remodel
Relocate existing transformer to 10 feet of building, we will shorten existing service entrance conductors as needed to new location. No work inside existing building to be done at this time. Called 1-16-18 for 1 month extension.NelsonThorpe Sarah 01/16/2018 9:07 AM Called 03/01/2018 for 1 bgillespie 03/01/2018 11:34 AMweek extension.
05/24/2017
05/25/2017
09/03/2018
03/07/2018

Locations

Permits

Permit Number: PREL201704144

Electrical
Finaled
05/25/2017
09/03/2018

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 6/26/2017 (10:00 - 12:00) 6/26/2017 06/26/2017
Corrections:


Miscellaneous/Other
Comment Only
06/26/2017
Site visit and underground at transformer OK Contractor in process of changing fuses at meter bank

Miscellaneous/Other
Outstanding
06/26/2017
Verify grounding and bonding at existing fused disconnect and CT cabinet. No main bond visible. CT cabinet and raceway are not properly bonded. Bring GEC connections into NEC compliance.

Electrical Rough-in Inspection Partial Pass 9/27/2017 (10:00 - 12:00) 9/27/2017 09/29/2017
Corrections:


Outstanding
09/27/2017
Bond service 1 GEC to service 2 GEC. Bond around water meter.

Electrical Final Inspection Passed 3/7/2018 (10:00 - 12:00) 3/7/2018 03/07/2018