PREL201704608
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 7/24/2017 (10:00 - 12:00) | 7/24/2017 | 07/24/2017 |
Corrections:
Miscellaneous/Other
Comment Only
07/24/2017
Partial wall RI
|
||||
Electrical Rough-in Inspection | Partial Pass | 7/26/2017 (10:00 - 12:00) | 7/26/2017 | 07/26/2017 |
Corrections:
Miscellaneous/Other
Comment Only
07/26/2017
800amp 120 - 208 v overhead
Call Xcell
|
||||
Electrical Rough-in Inspection | Partial Pass | 7/31/2017 (2:30 - 3:30) | 7/31/2017 | 07/31/2017 |
Corrections:
Miscellaneous/Other
Comment Only
07/31/2017
Wall RI
|
||||
Electrical Rough-in Inspection | Partial Pass | 8/7/2017 (10:00 - 12:00) | 8/7/2017 | 08/07/2017 |
Corrections:
Miscellaneous/Other
Comment Only
08/07/2017
Wall RI complete
|
||||
Electrical Rough-in Inspection | Passed | 9/20/2017 (2:30 - 3:30) | 9/20/2017 | 09/20/2017 |
Corrections:
Miscellaneous/Other
Comment Only
09/20/2017
Above ceiling OK- in progress
Ok to cover. Verbal - complete removal of temporary lighting.
|
||||
Electrical Final Inspection | Partial Pass | 9/22/2017 (10:00 - 12:00) | 9/22/2017 | 09/22/2017 |
Corrections:
Miscellaneous/Other
Outstanding
09/22/2017
At office area - exit light is required to be on same branch circuit as lighting in the area.
Change to circuit #4
|
||||
Miscellaneous/Other
Comment Only
09/22/2017
Rooftop ok
GFCI testing of receptacle outlets OK
Partial final- complete store fixtures and aquariums.
Egress illumination ok per NEC- except as noted.
|
||||
Electrical Final Inspection | Partial Pass | 10/6/2017 (12:30 - 2:30) | 10/6/2017 | 10/06/2017 |
Corrections:
Miscellaneous/Other
Comment Only
10/06/2017
Final complete pending sign installation.
Complete signage and call for final inspection.
|
||||
Electrical Final Inspection | Passed | 10/19/2017 (8:00 - 10:00) | 10/19/2017 | 10/19/2017 |
Corrections:
Miscellaneous/Other
Comment Only
10/19/2017
Signs are complete.
Final - approved.
|