PREL201705176
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 10/19/2017 (12:30 - 2:30) | 10/19/2017 | 10/20/2017 |
Corrections:
Miscellaneous/Other
Comment Only
10/20/2017
4th floor units - RI approved for NEC.
RI including FA cable installation and temperature control.
|
||||
Miscellaneous/Other
Comment Only
10/20/2017
Verbal with site foreman: verify compliance with all State Building code issues with others.
Building inspector will verify fire protection and accessibility issues. Fire inspector to verify and determine locations for fire related devices.
|
||||
Electrical Rough-in Inspection | Partial Pass | 10/26/2017 (12:30 - 2:30) | 10/26/2017 | 10/26/2017 |
Corrections:
Miscellaneous/Other
Comment Only
10/26/2017
RI - 3rd floor units, hall, elevator lobby (3and 4).
|
||||
Electrical Rough-in Inspection | Partial Pass | 11/8/2017 (2:30 - 3:30) | 11/8/2017 | 11/08/2017 |
Corrections:
Miscellaneous/Other
Comment Only
11/08/2017
RI - 2nd floor
|
||||
Electrical Rough-in Inspection | Partial Pass | 11/15/2017 (10:00 - 12:00) | 11/15/2017 | 11/15/2017 |
Corrections:
Miscellaneous/Other
Comment Only
11/15/2017
RI - 1st floor units.
|
||||
Electrical Rough-in Inspection | Partial Pass | 11/16/2017 (Morning) | 11/16/2017 | 11/16/2017 |
Corrections:
Miscellaneous/Other
Comment Only
11/16/2017
RI-1st floor elevator lobby and hallway.
RI-4th floor ceiling.
|
||||
Electrical Rough-in Inspection | Partial Pass | 11/29/2017 (8:00 - 10:00) | 11/29/2017 (AM) | 11/29/2017 |
Corrections:
Outstanding
11/29/2017
RI - 3rd Floor hall ceiling.
|
||||
Electrical Rough-in Inspection | Partial Pass | 12/4/2017 (2:30 - 3:30) | 12/4/2017 | 12/04/2017 |
Corrections:
Miscellaneous/Other
Comment Only
12/04/2017
Partial service: 300A/208V house meter and panel.
E-mailed Xcel.
|
||||
Electrical Rough-in Inspection | Partial Pass | 12/5/2017 (10:00 - 12:00) | 12/5/2017 | 12/05/2017 |
Corrections:
Miscellaneous/Other
Comment Only
12/05/2017
Follow up on grounding and bonding at services-OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 12/11/2017 (10:00 - 12:00) | 12/11/2017 | 12/11/2017 |
Corrections:
Miscellaneous/Other
Comment Only
12/11/2017
RI - 1st floor hall ceiling.
|
||||
Electrical Rough-in Inspection | Partial Pass | 1/8/2018 (8:00 - 10:00) | 1/8/2018 | 01/08/2018 |
Corrections:
Miscellaneous/Other
Comment Only
01/08/2018
32 meter bank inspection - 600A service
|
||||
Electrical Final Inspection | Partial Pass | 2/7/2018 (10:00 - 12:00) | 2/7/2018 | 02/07/2018 |
Corrections:
Miscellaneous/Other
Comment Only
02/07/2018
Partial final:
Units 400, 401, 403 (except decks).
Closet lite in 403 to meet NEC 410.16.
|
||||
Electrical Final Inspection | Partial Pass | 2/8/2018 (10:00 - 12:00) | 2/8/2018 | 02/08/2018 |
Corrections:
Miscellaneous/Other
Outstanding
02/08/2018
Partial final: 400, 305, 303.
Relocate closet lites: 401, 301.
GFI -protect deck outlets: 403, 405.
|
||||
Electrical Final Inspection | Partial Pass | 2/13/2018 (10:00 - 12:00) | 2/13/2018 | 02/13/2018 |
Corrections:
Miscellaneous/Other
Outstanding
02/13/2018
Partial final:
Rooms 200, 201, 203, 100, 101.
Room 205 has short circuit in kitchen circuits.
|
||||
Electrical Final Inspection | Partial Pass | 2/14/2018 (10:00 - 12:00) | 2/14/2018 | 02/14/2018 |
Corrections:
Miscellaneous/Other
Comment Only
02/14/2018
Final: units 103, 104, 105, 205.
|
||||
Electrical Final Inspection | Partial Pass | 2/15/2018 (10:00 - 12:00) | 2/15/2018 | 02/15/2018 |
Corrections:
Miscellaneous/Other
Comment Only
02/15/2018
Final - hallways and stairs.
Exit lites to check.
|
||||
Electrical Final Inspection | Partial Pass | 3/7/2018 (10:00 - 12:00) | 3/7/2018 | 03/07/2018 |
Corrections:
Miscellaneous/Other
Comment Only
03/07/2018
Final - Units 106, 107, 402, 404, 406, 407.
|
||||
Electrical Final Inspection | Passed | 3/8/2018 (10:00 - 12:00) | 3/8/2018 | 01/17/2019 |