Summary

PREL201705557
Electrical
Finaled
MOAC MALL HOLDINGS LLC
Alteration/Remodel
Install lighting and receptacles.
06/27/2017
06/28/2017
06/07/2021
09/01/2017

Locations

Permits

Permit Number: PREL201705557

Electrical
Finaled
06/28/2017
06/07/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 6/30/2017 (8:00 - 10:00) 6/30/2017 06/30/2017
Do not schedule until planning review is complete. kisaacson 06/28/2017 8:44 AM
Corrections:


Miscellaneous/Other
Outstanding
06/30/2017
RI - walls

Electrical Rough-in Inspection Partial Pass 7/11/2017 (8:00 - 3:30) 7/11/2017 07/11/2017
Corrections:


Miscellaneous/Other
Comment Only
07/11/2017
RI - ceiling (sales area - except N. side).

Electrical Rough-in Inspection Partial Pass 7/25/2017 (8:00 - 10:00) 7/25/2017 07/25/2017
Corrections:


Miscellaneous/Other
Comment Only
07/25/2017
RI - hard-lid ceilings.

Electrical Rough-in Inspection Partial Pass 8/17/2017 (10:00 - 12:00) 8/17/2017 08/17/2017
Corrections:


Miscellaneous/Other
Outstanding
08/17/2017
120v cords above ceiling require plenum rating. Sales floor fixtures require UL label. Pendant fixtures require UL label.

Electrical Rough-in Inspection Partial Pass 8/22/2017 (10:00 - 12:00) 8/22/2017 08/22/2017
Corrections:


Miscellaneous/Other
Comment Only
08/22/2017
Progress inspection- revisions of above plenum ceiling- ok. Type CMP cable installed, driver are in process of hard wiring. Driver replacement is class 2 and listed for LED use. Check completion at final inspection. LED strips bear UL listing label.

Miscellaneous/Other
Comment Only
08/22/2017
Verbal- OK to stock and bring in POS equipment. Install bolt and nut at raised cover outlet, secure 1900 box and MC cable at tasting station.

Electrical Rough-in Inspection Passed 8/25/2017 (8:00 - 10:00) 8/25/2017 08/25/2017
Corrections:


Miscellaneous/Other
Outstanding
08/25/2017
Install disconnect switches on floor fixtures and box signs. Independent evaluations required.

Electrical Final Inspection Passed 9/1/2017 (8:00 - 10:00) 9/1/2017 09/01/2017
Corrections:


Miscellaneous/Other
Comment Only
09/01/2017
Received independent evaluations for the unlisted lighting.