Summary

PREL201709619
Electrical
Finaled
TWIN CITY FED SAV & LOAN
Repair/Replace
Tenant build-out, The Joint Chiropractic.
10/09/2017
10/12/2017
05/14/2018
11/15/2017

Locations

Permits

Permit Number: PREL201709619

Electrical
Finaled

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 10/17/2017 (10:00 - 12:00) 10/17/2017 10/17/2017
Miscellaneous/Other
Comment Only
10/17/2017
RI OK For walls. HCFMC OK At treatment area. Re-feed existing to redundant grounding at treatment area. Call for above ceiling inspection.

Electrical Rough-in Inspection Passed w/ Conditions 11/2/2017 (10:00 - 12:00) 11/2/2017 11/02/2017
Miscellaneous/Other
Comment Only
11/02/2017
Above ceiling RI for power and lighting only.

Miscellaneous/Other
Outstanding
11/02/2017
Spoke to GC - sign electrical non- compliant. Limited energy work by others- non plenum cabling. Install to code by licensed contractor- with permit and inspection.

Electrical Final Inspection Passed 11/15/2017 (12:30 - 2:30) 11/15/2017 11/15/2017
Miscellaneous/Other
Comment Only
11/15/2017
Final OK. Sign limited energy by other permit. Power to sign by other permit.