PREL201709715
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 10/13/2017 (12:30 - 2:30) | 10/13/2017 | 10/13/2017 |
Corrections:
Miscellaneous/Other
Comment Only
10/13/2017
RI of bathrooms on 2nd level MOA 1C - OK including corridor
Complete power, light and fire alarm cable
Complete all demo
Verify LED power source at subsequent inspection- Class 2 wiring used.
|
||||
Electrical Rough-in Inspection | Partial Pass | 11/16/2017 (2:30 - 3:30) | 11/16/2017 | 11/16/2017 |
Corrections:
Miscellaneous/Other
Comment Only
11/16/2017
RI - 1st floor restrooms and corridor.
|
||||
Electrical Rough-in Inspection | Passed | 11/30/2017 (10:00 - 12:00) | 11/30/2017 | 11/30/2017 |
Corrections:
Miscellaneous/Other
Comment Only
11/30/2017
RI - back stairs and 1st floor corridor.
RI complete.
|
||||
Electrical Final Inspection | Partial Pass | 12/22/2017 (8:00 - 10:00) | 12/22/2017 | 12/22/2017 |
Corrections:
Miscellaneous/Other
Comment Only
12/22/2017
2nd floor bathrooms, family bathroom and personal needs room- part pass.
OK to use/ occupy.
Check LED drivers prior to final permit approval.
Verbal- replace non- GFCI receptacle with GFCI protection at family room bathroom.
Provide breaker lock-off at hand dryer.
|
||||
Electrical Final Inspection | Passed | 2/15/2018 (10:00 - 12:00) | 2/15/2018 | 02/15/2018 |