PREL201711358
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 1/24/2018 (8:00 - 10:00) | 1/24/2018 | 01/24/2018 |
Corrections:
Miscellaneous/Other
Comment Only
01/24/2018
Site visit and questions at site- verbal OK.
|
||||
Miscellaneous/Other
Outstanding
01/24/2018
Verify/ provide available fault current calculations for 200 amp house panels, 1200 amp tenant distribution. Verify availabile fault current at RTU's.
|
||||
Miscellaneous/Other
Outstanding
01/24/2018
Inspectior to notify Xcel for metering of 1200 Amp feeder. Feeder approved- contingent on approval of available fault current at equipment.
|
||||
Miscellaneous/Other
Outstanding
01/24/2018
Provide service receptacle outlets to code for HVAC installations.
|
||||
Miscellaneous/Other
Outstanding
01/24/2018
Panic hardware required at electrical room at tenant space.
|
||||
Miscellaneous/Other
Outstanding
01/24/2018
Provide roof access for RTU inspections when ready.
|
||||
Electrical Final Inspection | Not Ready | 3/8/2018 (12:30 - 2:30) | 3/8/2018 | 03/08/2018 |
Rescheduled from morning to afternoon with extra time allowed (per Tim Miller). Tim contacted project manager and is awaiting callback to discuss. ajacobson 03/07/2018 8:30 AM | ||||
Corrections:
Miscellaneous/Other
Comment Only
03/08/2018
Contractor called inspector and said they are not ready for final inspection and they will re-schedule.
|
||||
Electrical Final Inspection | Passed | 3/14/2018 (12:30 - 2:30) | 3/14/2018 | 03/14/2018 |
Corrections:
Miscellaneous/Other
Comment Only
03/14/2018
Final approved.
|