Summary

PREL201800066
Electrical
Closed
SCL HOLDINGS-THE PNT LLC
Alteration/Remodel
Wire 3 signs, 4 pendant lights.
01/03/2018
01/08/2018
01/05/2019
01/26/2019

Locations

Permits

Permit Number: PREL201800066

Electrical
Finaled
01/08/2018
01/05/2019

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Failed 1/18/2018 (10:00 - 12:00) 1/18/2018 01/18/2018
Corrections:


Miscellaneous/Other
Carried Forward
01/18/2018
All electrical work - including class 2 is required to be performed by a MN State Licensed Contractor.

Miscellaneous/Other
Carried Forward
01/18/2018
Non-plenum rated wiring installed in a return air ceiling space- including channel letter cable. Install to code.

Miscellaneous/Other
Carried Forward
01/18/2018
Channel letters appear to be NRTL listed and labeled. LED drivers not included in the listing. LED drivers are not listed equipment- recognized component only- install listed LED rated Class 2 drivers. Maintain separation between limited energy and power conductors at enclosure.

Electrical Final Inspection Not Ready 2/5/2018 (10:00 - 12:00) 2/5/2018 02/05/2018
Corrections:


Miscellaneous/Other
Carried Forward
02/05/2018
All electrical work - including class 2 is required to be performed by a MN State Licensed Contractor.

Miscellaneous/Other
Carried Forward
02/05/2018
Non-plenum rated wiring installed in a return air ceiling space- including channel letter cable. Install to code.

Miscellaneous/Other
Carried Forward
02/05/2018
Channel letters appear to be NRTL listed and labeled. LED drivers not included in the listing. LED drivers are not listed equipment- recognized component only- install listed LED rated Class 2 drivers. Maintain separation between limited energy and power conductors at enclosure.

Electrical Final Inspection Passed 2/6/2018 (8:00 - 10:00) 2/6/2018 02/06/2018
Corrections:


Miscellaneous/Other
Resolved
02/06/2018
All electrical work - including class 2 is required to be performed by a MN State Licensed Contractor.

Miscellaneous/Other
Resolved
02/06/2018
Non-plenum rated wiring installed in a return air ceiling space- including channel letter cable. Install to code.

Miscellaneous/Other
Resolved
02/06/2018
Channel letters appear to be NRTL listed and labeled. LED drivers not included in the listing. LED drivers are not listed equipment- recognized component only- install listed LED rated Class 2 drivers. Maintain separation between limited energy and power conductors at enclosure.

Lighting Inspection Failed 2/5/2018 2/19/2018 03/02/2018
Falafel signs - 125 NITS NMJ inspected on 3/1/18: N - 392, E - 396, and S -385 nits
Corrections:


Miscellaneous/Other
Outstanding
03/02/2018
Limited to 125 NITS - on 3/1/18 measured: N - 392, E - 396, and S -385 nits. Must be dimmed and re-inspected.

Lighting Inspection Failed 7/9/2018 07/09/2018
Falafel signs - 125 NITS NMJ inspected on 3/1/18: N - 392, E - 396, and S -385 nits LDP 7/7/18 all over 300
Lighting Inspection VOID 01/26/2019
Falafel signs - 125 NITS - NMJ inspected on 3/1/18: N - 392, E - 396, and S -385 nits - LDP 7/7/18 all over 300 After 6 attempts in two years to get compliance - case is expired and is in violation