PREL201800066
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Final Inspection | Failed | 1/18/2018 (10:00 - 12:00) | 1/18/2018 | 01/18/2018 |
|
Corrections:
Miscellaneous/Other
Carried Forward
01/18/2018
All electrical work - including class 2 is required to be performed by a MN State Licensed Contractor.
|
||||
|
Miscellaneous/Other
Carried Forward
01/18/2018
Non-plenum rated wiring installed in a return air ceiling space- including channel letter cable.
Install to code.
|
||||
|
Miscellaneous/Other
Carried Forward
01/18/2018
Channel letters appear to be NRTL listed and labeled.
LED drivers not included in the listing.
LED drivers are not listed equipment- recognized component only- install listed LED rated Class 2 drivers.
Maintain separation between limited energy and power conductors at enclosure.
|
||||
| Electrical Final Inspection | Not Ready | 2/5/2018 (10:00 - 12:00) | 2/5/2018 | 02/05/2018 |
|
Corrections:
Miscellaneous/Other
Carried Forward
02/05/2018
All electrical work - including class 2 is required to be performed by a MN State Licensed Contractor.
|
||||
|
Miscellaneous/Other
Carried Forward
02/05/2018
Non-plenum rated wiring installed in a return air ceiling space- including channel letter cable.
Install to code.
|
||||
|
Miscellaneous/Other
Carried Forward
02/05/2018
Channel letters appear to be NRTL listed and labeled.
LED drivers not included in the listing.
LED drivers are not listed equipment- recognized component only- install listed LED rated Class 2 drivers.
Maintain separation between limited energy and power conductors at enclosure.
|
||||
| Electrical Final Inspection | Passed | 2/6/2018 (8:00 - 10:00) | 2/6/2018 | 02/06/2018 |
|
Corrections:
Miscellaneous/Other
Resolved
02/06/2018
All electrical work - including class 2 is required to be performed by a MN State Licensed Contractor.
|
||||
|
Miscellaneous/Other
Resolved
02/06/2018
Non-plenum rated wiring installed in a return air ceiling space- including channel letter cable.
Install to code.
|
||||
|
Miscellaneous/Other
Resolved
02/06/2018
Channel letters appear to be NRTL listed and labeled.
LED drivers not included in the listing.
LED drivers are not listed equipment- recognized component only- install listed LED rated Class 2 drivers.
Maintain separation between limited energy and power conductors at enclosure.
|
||||
| Lighting Inspection | Failed | 2/5/2018 | 2/19/2018 | 03/02/2018 |
| Falafel signs - 125 NITS NMJ inspected on 3/1/18: N - 392, E - 396, and S -385 nits | ||||
|
Corrections:
Miscellaneous/Other
Outstanding
03/02/2018
Limited to 125 NITS - on 3/1/18 measured: N - 392, E - 396, and S -385 nits. Must be dimmed and re-inspected.
|
||||
| Lighting Inspection | Failed | 7/9/2018 | 07/09/2018 | |
| Falafel signs - 125 NITS NMJ inspected on 3/1/18: N - 392, E - 396, and S -385 nits LDP 7/7/18 all over 300 | ||||
| Lighting Inspection | VOID | 01/26/2019 | ||
| Falafel signs - 125 NITS - NMJ inspected on 3/1/18: N - 392, E - 396, and S -385 nits - LDP 7/7/18 all over 300 After 6 attempts in two years to get compliance - case is expired and is in violation | ||||