Permit Application Status

PREL201800674


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL201800674
Electrical
Finaled
KRAUS-ANDERSON INC
Alteration/Remodel
Build out of shell space into guitar center store.
01/23/2018
01/24/2018
09/19/2018
03/23/2018

Locations

Permits

Permit Number: PREL201800674

Electrical
Finaled

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 1/29/2018 (12:30 - 2:30) 1/29/2018 01/29/2018
Miscellaneous/Other
Comment Only
01/29/2018
RI Of walls OK

Electrical Rough-in Inspection Partial Pass 2/2/2018 (10:00 - 12:00) 2/2/2018 02/02/2018
Miscellaneous/Other
Comment Only
02/02/2018
Trenches ok for pvc conduits and floor boxes.

Electrical Rough-in Inspection Partial Pass 2/20/2018 (10:00 - 12:00) 2/20/2018 02/20/2018
Miscellaneous/Other
Comment Only
02/20/2018
Above ceiling at hard lid ok

Electrical Rough-in Inspection Passed w/ Conditions 3/7/2018 (12:30 - 2:30) 3/7/2018 03/08/2018
Miscellaneous/Other
Comment Only
03/08/2018
Above ceiling RI OK

Miscellaneous/Other
Outstanding
03/08/2018
At distribution equipment- based on available fault current at distribution verify AIC ratings of feeder circuit breakers. AIC Ratings must be equal to or greater than available fault current at feeder breakers. If using series ratings provide documentation to AHJ and provide labels to code.

Electrical Final Inspection Partial Pass 3/21/2018 (12:30 - 2:30) 3/21/2018 03/21/2018
Miscellaneous/Other
Comment Only
03/21/2018
Partial pass. OK to stock or bring in staff. Egress lighting function OK. Plug checks OK. Walk through with site foreman OK. Sign electrical work by others on separate electrical permit.

Miscellaneous/Other
Outstanding
03/21/2018
LED display lighting to complete. Drivers and LED tape listing OK. Missing panel directory. Install breaker lock off at hand dryers. Call for final re-inspection when work is substantially complete.

Electrical Final Inspection Passed 3/23/2018 (12:30 - 2:30) 3/23/2018 03/23/2018
Miscellaneous/Other
Comment Only
03/23/2018
Final complete.