PREL201801569
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Final Inspection | Pending | |||
| Electrical Rough-in Inspection | Pending | |||
| Electrical Rough-in Inspection | Partial Pass | 2/27/2018 (10:00 - 12:00) | 2/27/2018 | 02/27/2018 |
|
Corrections:
No building permit card on site or available
Comment Only
02/27/2018
No building permit card on site or available
|
||||
|
Remove all abandon limited energy wiring – abandoned phone, security, data, coax and the like shall be removed and remainder independently supported
Outstanding
02/27/2018
Remove all abandon limited energy wiring – abandoned phone, security, data, coax and the like shall be removed and remainder independently supported/secured.
|
||||
|
Miscellaneous/Other
Outstanding
02/27/2018
Fire alarm cable work requires electrical permit and inspection.
|
||||
|
Tamper resistant receptacle outlets required- type TR
Outstanding
02/27/2018
Tamper resistant receptacle outlets required- type TR - new and existing.
|
||||
|
Miscellaneous/Other
Comment Only
02/27/2018
Wall RI OK
|
||||