PREL201802906
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Rough-in Inspection | Failed | 4/9/2018 (2:30 - 3:30) | 4/9/2018 | 04/10/2018 |
|
Corrections:
Miscellaneous/Other
Carried Forward
04/10/2018
Time of sale work.
Minimum size grounding electrode conductor size for 200 amp service is #4 AWG.
Must locate where the service grounding electrode conductor is connected to city water piping and bond around water meter.
|
||||
|
Miscellaneous/Other
Carried Forward
04/10/2018
Branch circuit extension- requires AFCI protection for replacement or new receptacle outlets.
Receptacle outlets must be type TR - tamper resistant.
Improper wiring and reverse polarity at installation near gas log.
Wire to code.
|
||||
|
Miscellaneous/Other
Carried Forward
04/10/2018
No power at the bathroom replacement receptacle outlet at sink near tub.
Note: this outlet is Type TR and when properly installed has GFCI protection.
|
||||
|
Miscellaneous/Other
Comment Only
04/10/2018
Other electrical TOS items are minor work and do not require electrical permit.
|
||||
| Electrical Rough-in Inspection | Passed | 4/18/2018 (8:00 - 10:00) | 4/18/2018 | 04/18/2018 |
|
Corrections:
Miscellaneous/Other
Outstanding
04/10/2018
Time of sale work.
Minimum size grounding electrode conductor size for 200 amp service is #4 AWG.
Must locate where the service grounding electrode conductor is connected to city water piping and bond around water meter.
|
||||
|
Miscellaneous/Other
Outstanding
04/10/2018
Branch circuit extension- requires AFCI protection for replacement or new receptacle outlets.
Receptacle outlets must be type TR - tamper resistant.
Improper wiring and reverse polarity at installation near gas log.
Wire to code.
|
||||
|
Miscellaneous/Other
Outstanding
04/10/2018
No power at the bathroom replacement receptacle outlet at sink near tub.
Note: this outlet is Type TR and when properly installed has GFCI protection.
|
||||
| Electrical Final Inspection | Passed | 04/18/2018 | ||