Summary

PREL201802906
Electrical
Finaled
Vogi, Robert & Michelle
Repair/Replace
All hazardous items on the TOS
04/05/2018
04/05/2018
10/15/2018
04/18/2018

Locations

Permits

Permit Number: PREL201802906

Electrical
Finaled
04/05/2018
10/15/2018

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Failed 4/9/2018 (2:30 - 3:30) 4/9/2018 04/10/2018
Corrections:


Miscellaneous/Other
Carried Forward
04/10/2018
Time of sale work. Minimum size grounding electrode conductor size for 200 amp service is #4 AWG. Must locate where the service grounding electrode conductor is connected to city water piping and bond around water meter.

Miscellaneous/Other
Carried Forward
04/10/2018
Branch circuit extension- requires AFCI protection for replacement or new receptacle outlets. Receptacle outlets must be type TR - tamper resistant. Improper wiring and reverse polarity at installation near gas log. Wire to code.

Miscellaneous/Other
Carried Forward
04/10/2018
No power at the bathroom replacement receptacle outlet at sink near tub. Note: this outlet is Type TR and when properly installed has GFCI protection.

Miscellaneous/Other
Comment Only
04/10/2018
Other electrical TOS items are minor work and do not require electrical permit.

Electrical Rough-in Inspection Passed 4/18/2018 (8:00 - 10:00) 4/18/2018 04/18/2018
Corrections:


Miscellaneous/Other
Outstanding
04/10/2018
Time of sale work. Minimum size grounding electrode conductor size for 200 amp service is #4 AWG. Must locate where the service grounding electrode conductor is connected to city water piping and bond around water meter.

Miscellaneous/Other
Outstanding
04/10/2018
Branch circuit extension- requires AFCI protection for replacement or new receptacle outlets. Receptacle outlets must be type TR - tamper resistant. Improper wiring and reverse polarity at installation near gas log. Wire to code.

Miscellaneous/Other
Outstanding
04/10/2018
No power at the bathroom replacement receptacle outlet at sink near tub. Note: this outlet is Type TR and when properly installed has GFCI protection.

Electrical Final Inspection Passed 04/18/2018