PREL201804443
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Final Inspection | Failed | 11/8/2018 (10:00 - 12:00) | 11/8/2018 (AM) | 11/08/2018 |
|
Corrections:
Miscellaneous/Other
Carried Forward
11/08/2018
Work covered prior to inspection- remove and open t check visually.
Verify cable secure and support. Verify luminarie secured to grid.
|
||||
|
Miscellaneous/Other
Carried Forward
11/08/2018
Contractor to verify EM lighting requirements- exit lighting provided but no EM illumination.
|
||||
|
Miscellaneous/Other
Carried Forward
11/08/2018
Provide Type TR receptacle outlets- with GFCI protection.
Provide breaker lock off device for hand dryers.
Provide access to electrical panel(s).
Call for reinspection.
|
||||
| Electrical Final Inspection | Failed | 1/15/2019 (8:00 - 10:00) | 1/15/2019 (AM) | 01/15/2019 |
|
Corrections:
Miscellaneous/Other
Outstanding
01/15/2019
Work covered prior to inspection- remove and open t check visually.
Verify cable secure and support. Verify luminarie secured to grid.
|
||||
|
Miscellaneous/Other
Outstanding
01/15/2019
Contractor to verify EM lighting requirements- exit lighting provided but no EM illumination.
|
||||
|
Miscellaneous/Other
Outstanding
01/15/2019
Provide Type TR receptacle outlets- with GFCI protection.
Provide breaker lock off device for hand dryers.
Provide access to electrical panel(s).
Call for reinspection.
|
||||
|
Miscellaneous/Other
Outstanding
01/15/2019
No call for reinspection. Luminaries are not attached to grid.
Open box at ceiling of men's room.
No EM lighting installation- EM is called out on plan.
|
||||
|
Miscellaneous/Other
Outstanding
01/15/2019
Open line voltage wiring at women's bathroom to LED luminaries- install to code.
|
||||
| Electrical Final Inspection | Failed | 01/15/2019 | ||
|
Corrections:
Miscellaneous/Other
Carried Forward
01/15/2019
Work covered prior to inspection- remove and open t check visually.
Verify cable secure and support. Verify luminarie secured to grid.
|
||||
|
Miscellaneous/Other
Carried Forward
01/15/2019
Contractor to verify EM lighting requirements- exit lighting provided but no EM illumination.
|
||||
|
Miscellaneous/Other
Carried Forward
01/15/2019
Provide Type TR receptacle outlets- with GFCI protection.
Provide breaker lock off device for hand dryers.
Provide access to electrical panel(s).
Call for reinspection.
|
||||
|
Miscellaneous/Other
Carried Forward
01/15/2019
No call for reinspection. Luminaries are not attached to grid.
Open box at ceiling of men's room.
No EM lighting installation- EM is called out on plan.
|
||||
|
Miscellaneous/Other
Carried Forward
01/15/2019
Open line voltage wiring at women's bathroom- install LED alighting to code.
|
||||
| Electrical Final Inspection | Passed w/ Conditions | 4/9/2019 (8:00 - 10:00) | 4/9/2019 (AM) | 04/09/2019 |
|
Corrections:
Miscellaneous/Other
Comment Only
04/09/2019
Work covered prior to inspection- remove and open t check visually.
Verify cable secure and support. Verify luminarie secured to grid.
|
||||
|
Miscellaneous/Other
Comment Only
04/09/2019
Contractor to verify EM lighting requirements- exit lighting provided but no EM illumination.
|
||||
|
Miscellaneous/Other
Outstanding
01/15/2019
Provide Type TR receptacle outlets- with GFCI protection.
Provide breaker lock off device for hand dryers.
Provide access to electrical panel(s).
Call for reinspection.
|
||||
|
Miscellaneous/Other
Comment Only
04/09/2019
PNo call for reinspection. Luminaries are not attached to grid.
Open box at ceiling of men's room.
No EM lighting installation- EM is called out on plan.
|
||||
|
Miscellaneous/Other
Comment Only
04/09/2019
Open line voltage wiring at women's bathroom- install LED alighting to code.
|
||||
|
Miscellaneous/Other
Comment Only
04/09/2019
Contractor to label all bathroom circuits.
Contractor to provide breaker lock- offs for hand dryers for disconnect means.
|
||||