PREL201806143
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 9/26/2018 (8:00 - 10:00) | 9/26/2018 | 09/26/2018 |
Corrections:
Miscellaneous/Other
Comment Only
09/26/2018
Site visit- city reviewed plan not on site.
Visual ok at slab work.
|
||||
Electrical Rough-in Inspection | Partial Pass | 10/26/2018 (8:00 - 10:00) | 10/26/2018 (AM) | 10/26/2018 |
Corrections:
Miscellaneous/Other
Comment Only
10/26/2018
Relocation of temp service. OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 1/7/2019 (8:00 - 10:00) | 1/7/2019 (AM) | 01/07/2019 |
Corrections:
Miscellaneous/Other
Comment Only
01/07/2019
Site visit only
|
||||
Electrical Rough-in Inspection | Partial Pass | 1/15/2019 (8:00 - 10:00) | 1/15/2019 (AM) | 01/15/2019 |
Corrections:
Miscellaneous/Other
Comment Only
01/15/2019
Bonding OK at two wet niche fixtures.
Call for all bonding inspections.
|
||||
Electrical Rough-in Inspection | Partial Pass | 3/19/2019 (8:00 - 10:00) | 3/19/2019 (AM) | 03/19/2019 |
Corrections:
Miscellaneous/Other
Comment Only
03/19/2019
Questions at site.
Exterior walls at first level RI OK.
Exterior walls at 2nd and 3rd floors - limited view and access as insulation had been installed prior to inspection.
Partial RI on units at 2nd floor.
|
||||
Electrical Rough-in Inspection | Partial Pass | 3/20/2019 (10:00 - 12:00) | 3/20/2019 (AM) | 03/20/2019 |
Corrections:
Miscellaneous/Other
Comment Only
03/20/2019
Progress inspection at 2nd floor units.
Inspector note there will be multiple RI inspection at units.
2nd floor guest suites RI OK.
2nd floor guest rooms partial, OK.
|
||||
Electrical Rough-in Inspection | Partial Pass | 3/22/2019 (8:00 - 10:00) | 3/22/2019 (AM) | 03/22/2019 |
Corrections:
Miscellaneous/Other
Comment Only
03/22/2019
Units at 2nd floor RI OK
|
||||
Miscellaneous/Other
Comment Only
03/22/2019
3rd floor guest rooms and 1/2 of the floor
of the suites RI OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 3/25/2019 (10:00 - 12:00) | 3/25/2019 (AM) | 03/25/2019 |
Corrections:
Miscellaneous/Other
Comment Only
03/25/2019
RI OK at 3rd floor units.
RI OK at 8 of 14 1st floor units.
|
||||
Electrical Rough-in Inspection | Partial Pass | 3/29/2019 (10:00 - 12:00) | 3/29/2019 (AM) | 03/29/2019 |
Corrections:
Miscellaneous/Other
Comment Only
03/29/2019
RI OK @ 1st floor suites. 14 total.
|
||||
Electrical Rough-in Inspection | Partial Pass | 4/8/2019 (8:00 - 10:00) | 4/8/2019 (AM) | 04/08/2019 |
Corrections:
Miscellaneous/Other
Comment Only
04/08/2019
RI OK For 4th floor guest rooms
|
||||
Electrical Rough-in Inspection | Partial Pass | 4/9/2019 (12:30 - 2:30) | 4/9/2019 (PM) | 04/09/2019 |
Corrections:
Miscellaneous/Other
Comment Only
04/09/2019
RI OK For 4th floor units. RI OK for 1st floor units.
|
||||
Electrical Rough-in Inspection | Partial Pass | 4/10/2019 (12:30 - 2:30) | 4/10/2019 (PM) | 04/10/2019 |
Corrections:
Miscellaneous/Other
Comment Only
04/10/2019
4th floor and 3rd floor corridor RI OK.
Unit equipment to be on the same branch circuit as normal lighting in the area
|
||||
Electrical Rough-in Inspection | Partial Pass | 4/18/2019 (12:30 - 2:30) | 4/18/2019 (PM) | 04/18/2019 |
Corrections:
Miscellaneous/Other
Comment Only
04/18/2019
2nd floor corridor OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 5/1/2019 (8:00 - 3:30) | 5/1/2019 (AM) | 05/01/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
05/01/2019
Site visit and walk through with contractor.
Verify available fault current at exterior lighting contractor.
|
||||
Miscellaneous/Other
Carried Forward
05/01/2019
Site visit and walk through with contractor.
Verify available fault current at exterior lighting contractor.
|
||||
Electrical Rough-in Inspection | Partial Pass | 5/22/2019 (8:00 - 10:00) | 5/22/2019 (AM) | 05/22/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
05/22/2019
Site visit and walk through with contractor.
Verify available fault current at exterior lighting contractor.
|
||||
Miscellaneous/Other
Comment Only
05/22/2019
Site visit and walk through with contractor.
Verify available fault current at exterior lighting contractor.
|
||||
Miscellaneous/Other
Comment Only
05/22/2019
Bonding at pool - 4 corners to pool shell, wet niche lights, cups for hand rails and ladders.
|
||||
Miscellaneous/Other
Carried Forward
05/22/2019
Verify mount for handicapped pool access equipment and bond to any re-bar at perimeter.
Call for additional bonding inspections as needed.
|
||||
Miscellaneous/Other
Comment Only
05/22/2019
Walk through at first floor corridor OK.
|
||||
Electrical Rough-in Inspection | Partial Pass | 5/30/2019 (12:30 - 2:30) | 5/30/2019 (PM) | 05/30/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
05/30/2019
Site visit and walk through with contractor.
Verify available fault current at exterior lighting contractor.
|
||||
Miscellaneous/Other
Comment Only
05/30/2019
Verify mount for handicapped pool access equipment and bond to any re-bar at perimeter.
Call for additional bonding inspections as needed.
|
||||
Miscellaneous/Other
Comment Only
05/30/2019
1st floor ceilings and common areas- RI OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 6/6/2019 (Morning) | 6/6/2019 (AM) | 06/06/2019 |
Corrections:
Miscellaneous/Other
Resolved
06/06/2019
Site visit and walk through with contractor.
Verify available fault current at exterior lighting contractor.
|
||||
Miscellaneous/Other
Comment Only
06/06/2019
4th floor units hard lid ceilings OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 6/13/2019 (12:30 - 2:30) | 6/13/2019 (PM) | 06/14/2019 |
Corrections:
Miscellaneous/Other
Comment Only
06/14/2019
4th floor corridor above ceiling OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 7/1/2019 (12:30 - 2:30) | 7/1/2019 (PM) | 07/01/2019 |
Corrections:
Miscellaneous/Other
Comment Only
07/01/2019
3 floor units- hard lid above ceiling RI OK
1/2 3rd floor corridor above hard lid ceilings RI
OK.
|
||||
Electrical Rough-in Inspection | Partial Pass | 7/3/2019 (12:30 - 2:30) | 7/3/2019 (PM) | 07/03/2019 |
Corrections:
Miscellaneous/Other
Comment Only
07/03/2019
3 floor corridor hard lid RI OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 7/11/2019 (8:00 - 10:00) | 7/11/2019 (AM) | 07/11/2019 |
Corrections:
Miscellaneous/Other
Outstanding
07/11/2019
Bond at CT cabinet.
|
||||
Miscellaneous/Other
Comment Only
07/11/2019
Service pass for release to Xcel.
|
||||
Miscellaneous/Other
Outstanding
07/11/2019
Verify series ratings at all panelboards.
Provide documentation.
|
||||
Electrical Rough-in Inspection | Partial Pass | 7/12/2019 (10:00 - 12:00) | 7/12/2019 (AM) | 07/12/2019 |
release service to Xcel 4000 AMP 120/208 Volt tmiller 07/15/2019 3:48 PM | ||||
Corrections:
Miscellaneous/Other
Comment Only
07/12/2019
2nd floor unit hard lid ceilings RI - OK
|
||||
Miscellaneous/Other
Comment Only
07/12/2019
4000 AMP 3 phase 120/208 volt service
OK to release to Xcel.
Correction OK at CT cabinet.
Verify series ratings at panel boards.
|
||||
Electrical Rough-in Inspection | Partial Pass | 7/18/2019 (12:30 - 2:30) | 7/18/2019 (PM) | 07/18/2019 |
Corrections:
Miscellaneous/Other
Comment Only
07/18/2019
2nd floor main corridor above ceiling RI OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 7/29/2019 (10:00 - 12:00) | 7/29/2019 (AM) | 07/29/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
07/29/2019
Front canopy lighting RI
|
||||
Electrical Rough-in Inspection | Partial Pass | 8/9/2019 (12:30 - 2:30) | 8/9/2019 (PM) | 08/09/2019 |
Corrections:
Miscellaneous/Other
Comment Only
08/09/2019
Front canopy lighting RI
|
||||
Miscellaneous/Other
Comment Only
08/09/2019
Canopy ok to cover- RI OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 9/5/2019 (10:00 - 12:00) | 9/5/2019 (AM) | 09/05/2019 |
Corrections:
Miscellaneous/Other
Comment Only
09/05/2019
1st floor corridor and units - hard lid ceilings RI-OK
|
||||
Miscellaneous/Other
Carried Forward
09/05/2019
Verify gen-set listings.
|
||||
Electrical Rough-in Inspection | Partial Pass | 9/12/2019 (12:30 - 2:30) | 9/12/2019 (PM) | 09/12/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
09/12/2019
Verify gen-set listings.
|
||||
Miscellaneous/Other
Comment Only
09/12/2019
Above ceiling at pool deck area.
call for re-inspection for bonding of all fixed metal parts.
Luminaires will require GFCI protection.
Verify "lens" type- totally enclosed required where located less than 5 foot horizontal from inside wall of pool.
|
||||
Electrical Rough-in Inspection | Partial Pass | 9/16/2019 (12:30 - 2:30) | 9/16/2019 (PM) | 09/16/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
09/16/2019
Verify gen-set listings.
|
||||
Miscellaneous/Other
Comment Only
09/16/2019
Bonding OK at above pool and pool deck.
|
||||
Electrical Rough-in Inspection | Partial Pass | 9/26/2019 (8:00 - 10:00) | 9/26/2019 (AM) | 09/26/2019 |
Corrections:
Miscellaneous/Other
Resolved
09/26/2019
Verify gen-set listings.
|
||||
Miscellaneous/Other
Comment Only
09/26/2019
Above ceiling at main floor lobby and common areas RI- OK.
|
||||
Electrical Rough-in Inspection | Partial Pass | 9/27/2019 (12:30 - 2:30) | 9/27/2019 (PM) | 09/27/2019 |
Corrections:
Miscellaneous/Other
Comment Only
09/27/2019
Ceiling RI OK at main level- gym area
|
||||
Electrical Rough-in Inspection | Partial Pass | 10/22/2019 (10:00 - 12:00) | 10/22/2019 (AM) | 10/22/2019 |
Corrections:
Miscellaneous/Other
Comment Only
10/22/2019
4th floor corridor- ceilings OK
|
||||
Electrical Final Inspection | Partial Pass | 10/30/2019 (10:00 - 12:00) | 10/30/2019 (AM) | 10/30/2019 |
Corrections:
Miscellaneous/Other
Comment Only
10/30/2019
Plug checks and walk through Units- # 401 through #432.
Verbal- provide GFCI protection for receptacle wall outlet within six foot of sink.
Install box extension at bathroom wall openings.
|
||||
Electrical Final Inspection | Partial Pass | 11/1/2019 (10:00 - 12:00) | 11/1/2019 (AM) | 11/01/2019 |
Corrections:
Miscellaneous/Other
Comment Only
11/01/2019
Partial final- 4th Floor units- Verify AFCI
|
||||
Electrical Final Inspection | Partial Pass | 11/4/2019 (10:00 - 12:00) | 11/4/2019 (AM) | 11/04/2019 |
Corrections:
Miscellaneous/Other
Comment Only
11/04/2019
Unit walk through- final #301- #331 odd side OK
|
||||
Electrical Final Inspection | Not Ready | 11/6/2019 (10:00 - 12:00) | 11/6/2019 (AM) | 11/06/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
11/06/2019
AFCI protection must comply with NEC 210.12 (C)
|
||||
Electrical Final Inspection | Partial Pass | 11/13/2019 (10:00 - 12:00) | 11/13/2019 (AM) | 11/13/2019 |
Corrections:
Miscellaneous/Other
Outstanding
11/06/2019
AFCI protection must comply with NEC 210.12 (C)
|
||||
Miscellaneous/Other
Comment Only
11/13/2019
Final units - 302 - 332 even number rooms and 335-355 odd number rooms.
OK
|
||||
Electrical Final Inspection | Partial Pass | 11/15/2019 (10:00 - 12:00) | 11/15/2019 (AM) | 11/15/2019 |
Corrections:
Miscellaneous/Other
Comment Only
11/15/2019
3rd floor units- plug check complete
|
||||
Miscellaneous/Other
Comment Only
11/15/2019
Elevator equipment room OK
|
||||
Miscellaneous/Other
Comment Only
11/15/2019
Listing and labeling of laundry room equipment OK
|
||||
Electrical Final Inspection | Partial Pass | 11/19/2019 (10:00 - 12:00) | 11/19/2019 (AM) | 11/19/2019 |
Corrections:
Miscellaneous/Other
Comment Only
11/19/2019
Walkthrough of units # 201 through # 232
plug checks OK
|
||||
Electrical Final Inspection | Partial Pass | 11/21/2019 (10:00 - 12:00) | 11/21/2019 (AM) | 11/21/2019 |
Corrections:
Miscellaneous/Other
Comment Only
11/21/2019
Plug checks OK at # 101 through # 114
|
||||
Electrical Final Inspection | Partial Pass | 11/22/2019 (10:00 - 12:00) | 11/22/2019 (AM) | 11/22/2019 |
Corrections:
Miscellaneous/Other
Comment Only
11/22/2019
1st floor ceilings RI OK
|
||||
Miscellaneous/Other
Outstanding
11/22/2019
Laundry chute control box is listed but does not bear Class 2 labels- treat as power circuit- must be performed by licensed electrical contractor
|
||||
Miscellaneous/Other
Outstanding
11/22/2019
Verify SCCR ratings to OCP settings per nameplate at transfer switch
|
||||
Electrical Final Inspection | Partial Pass | 11/25/2019 (10:00 - 12:00) | 11/25/2019 (AM) | 11/25/2019 |
Corrections:
Miscellaneous/Other
Comment Only
11/25/2019
Review/ inspection of HVAC equipment,
Including roof top units- verbal for OCP sizing at mini split units.
|
||||
Electrical Final Inspection | Partial Pass | 11/26/2019 (10:00 - 12:00) | 11/26/2019 (AM) | 11/26/2019 |
Corrections:
Miscellaneous/Other
Comment Only
11/26/2019
2nd Floor units- plug check OK- complete
|
||||
Electrical Final Inspection | Partial Pass | 11/27/2019 (10:00 - 12:00) | 11/27/2019 (AM) | 11/27/2019 |
Corrections:
Miscellaneous/Other
Comment Only
11/27/2019
1st floor units - plug checks OK
|
||||
Electrical Final Inspection | Partial Pass | 12/2/2019 (10:00 - 12:00) | 12/2/2019 (AM) | 12/02/2019 |
Corrections:
Miscellaneous/Other
Comment Only
12/02/2019
Power outage at inspection.
Walk through with contractor for life safety lighting inspection- function OK
|
||||
Electrical Final Inspection | Passed | 12/3/2019 (10:00 - 12:00) | 12/3/2019 (AM) | 12/03/2019 |
Corrections:
Miscellaneous/Other
Comment Only
12/03/2019
Testing of AFCI function for units without panelboard in unit- OK
|
||||
Electrical Final Inspection | Partial Pass | 12/4/2019 (10:00 - 12:00) | 12/4/2019 (AM) | 12/04/2019 |
Corrections:
Miscellaneous/Other
Comment Only
12/04/2019
Routine walk through with foreman- laundry whips OK
Exterior lighting requires readily accessible GFCI protection.
|
||||
Miscellaneous/Other
Comment Only
12/04/2019
Replacement of non- TR modular receptacles at headboards- spot checks for replacement OK
|
||||
Electrical Final Inspection | Partial Pass | 12/5/2019 (10:00 - 12:00) | 12/5/2019 (AM) | 12/05/2019 |
Corrections:
Miscellaneous/Other
Comment Only
12/05/2019
Progress inspection OK- signed permit card for partial final
|
||||
Electrical Final Inspection | Partial Pass | 12/6/2019 (10:00 - 12:00) | 12/6/2019 (AM) | 12/06/2019 |
Corrections:
Miscellaneous/Other
Comment Only
12/06/2019
Progress inspection at pool equipment room
|
||||
Electrical Final Inspection | Partial Pass | 12/12/2019 (10:00 - 12:00) | 12/12/2019 (AM) | 12/12/2019 |
Corrections:
Miscellaneous/Other
Comment Only
12/12/2019
Routine progress inspection
|
||||
Electrical Final Inspection | Partial Pass | 12/13/2019 (10:00 - 12:00) | 12/13/2019 (AM) | 12/13/2019 |
Corrections:
Miscellaneous/Other
Comment Only
12/13/2019
Review of modifications at elevator equipment room.
|
||||
Electrical Final Inspection | Partial Pass | 12/20/2019 (10:00 - 12:00) | 12/20/2019 (AM) | 12/20/2019 |
Corrections:
Miscellaneous/Other
Comment Only
12/20/2019
Pool and pool equipment room final OK
|
||||
Electrical Final Inspection | Passed | 12/23/2019 (10:00 - 12:00) | 12/23/2019 (AM) | 12/23/2019 |
Corrections:
Miscellaneous/Other
Comment Only
12/23/2019
Final electrical inspection approved.
|