Permit Application Status

PREL201806824


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL201806824
Electrical
Finaled
MOAC MALL HOLDINGS LLC
Other
XD Ride - Mall of America (88252)
07/02/2018
07/18/2018
04/29/2019
10/31/2018

Locations

Permits

Permit Number: PREL201806824

Electrical
Finaled
07/18/2018
04/29/2019

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 7/26/2018 (8:00 - 10:00) 7/26/2018 07/26/2018
Corrections:


Miscellaneous/Other
Comment Only
07/26/2018
RI of theatre walls and ceiling only - OK Separate permit to be pulled for FA and temp controls. GC made aware.

Electrical Rough-in Inspection Partial Pass 8/2/2018 (10:00 - 12:00) 8/2/2018 08/02/2018
7/24/2018 inspection was canceled per Rick. ajacobson 07/31/2018 9:19 AM
Corrections:


Miscellaneous/Other
Comment Only
08/02/2018
Wall RI Show window receptacles needed

Electrical Rough-in Inspection Passed 8/8/2018 (8:00 - 10:00) 8/8/2018 08/08/2018
Corrections:


Miscellaneous/Other
Comment Only
08/08/2018
RI OK @ hard lid ceilings.

Electrical Rough-in Inspection Passed 9/7/2018 (8:00 - 10:00) 9/7/2018 09/07/2018
Corrections:


Miscellaneous/Other
Comment Only
09/07/2018
RI OK at raised floor in equipment room area.

Miscellaneous/Other
Comment Only
09/07/2018
RI above drop ceiling OK- verbal to tie off independent support wires

Electrical Final Inspection Failed 09/28/2018
Corrections:


Miscellaneous/Other
Carried Forward
09/28/2018
Site visit only. Non plenum limited energy cables installed by tenant- remove all non rated cable. All electrical installation is required to be performed by a State of Minnesota licensed contractor. Call for new rough in inspection of this scope of work- this was given to the general contractor as a verbal order.

All electrical equipment, machines or apparatus are required to be National Recognized Testing Laboratory certified/listed/labeled- NRTL certified
Carried Forward
09/28/2018
All electrical equipment, machines or apparatus are required to be National Recognized Testing Laboratory certified/listed/labeled- NRTL certified. Independent third party evaluation is permitted for unlisted installations and equipment.

Electrical Final Inspection Partial Pass 10/29/2018 (8:00 - 10:00) 10/29/2018 (AM) 10/29/2018
Corrections:


Miscellaneous/Other
Resolved
10/29/2018
Site visit only. Non plenum limited energy cables installed by tenant- remove all non rated cable. All electrical installation is required to be performed by a State of Minnesota licensed contractor. Call for new rough in inspection of this scope of work- this was given to the general contractor as a verbal order.

All electrical equipment, machines or apparatus are required to be National Recognized Testing Laboratory certified/listed/labeled- NRTL certified
Comment Only
10/29/2018
All electrical equipment, machines or apparatus are required to be National Recognized Testing Laboratory certified/listed/labeled- NRTL certified. Independent third party evaluation is permitted for unlisted installations and equipment.

Miscellaneous/Other
Carried Forward
10/29/2018
Electrical installation OK. Need copy of independent third party evaluation for review. OK to stock or train.

Electrical Final Inspection Passed 10/31/2018
Corrections:


Miscellaneous/Other
Resolved
10/31/2018
Electrical installation OK. Need copy of independent third party evaluation for review. OK to stock or train.

Miscellaneous/Other
Comment Only
10/31/2018
Independent third party evaluation received. Final OK.