PREL201807127
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 8/10/2018 (2:30 - 3:30) | 8/10/2018 | 08/10/2018 |
Contractor canceled roughin on same day. Notified Tim Miller. ajacobson 08/07/2018 8:36 AM | ||||
Corrections:
Miscellaneous/Other
Comment Only
08/10/2018
UG OK at slab.
|
||||
Miscellaneous/Other
Comment Only
08/10/2018
Concrete encased electrode present at future service location.
|
||||
Electrical Rough-in Inspection | Partial Pass | 9/7/2018 (10:00 - 12:00) | 9/7/2018 | 09/07/2018 |
Corrections:
Miscellaneous/Other
Comment Only
09/07/2018
No permit card on site.
RI OK at walls and exterior soffit.
|
||||
Electrical Rough-in Inspection | Partial Pass | 10/2/2018 (8:00 - 10:00) | 10/2/2018 | 10/02/2018 |
Corrections:
Miscellaneous/Other
Comment Only
10/02/2018
Above drop ceiling OK for power and lighting.
|
||||
Electrical Final Inspection | Failed | 10/10/2018 (2:30 - 3:30) | 10/10/2018 | 10/10/2018 |
Corrections:
Provide and label available fault current at service location
Carried Forward
10/10/2018
Provide arc flash warning labels.
|
||||
Miscellaneous/Other
Carried Forward
10/10/2018
Show window receptacles required.
|
||||
Miscellaneous/Other
Carried Forward
10/10/2018
No roof access.
|
||||
Miscellaneous/Other
Carried Forward
10/10/2018
Complete all installations.
|
||||
Miscellaneous/Other
Carried Forward
10/10/2018
Check parking lot lighting poles for bonding at next inspection.
#14 AWG on 20 amp circuit.
|
||||
Miscellaneous/Other
Carried Forward
10/10/2018
Verify debating at raceway with 10 current carrying conductors.
|
||||
Miscellaneous/Other
Carried Forward
10/10/2018
Verify location of grounding electrode conductor connection- if to electrode that is not encased then connection must be accessible.
|
||||
Electrical Final Inspection | Passed | 10/30/2018 (8:00 - 10:00) | 10/30/2018 (AM) | 10/30/2018 |
Corrections:
Provide and label available fault current at service location
Resolved
10/30/2018
Provide arc flash warning labels.
|
||||
Miscellaneous/Other
Resolved
10/30/2018
Show window receptacles required.
|
||||
Miscellaneous/Other
Resolved
10/30/2018
No roof access.
|
||||
Miscellaneous/Other
Resolved
10/30/2018
Complete all installations.
|
||||
Miscellaneous/Other
Resolved
10/30/2018
Check parking lot lighting poles for bonding at next inspection.
#14 AWG on 20 amp circuit.
|
||||
Miscellaneous/Other
Resolved
10/30/2018
Verify debating at raceway with 10 current carrying conductors.
|
||||
Miscellaneous/Other
Resolved
10/30/2018
Verify location of grounding electrode conductor connection- if to electrode that is not encased then connection must be accessible.
|
||||
Lighting Inspection Sign | Passed | 11/19/2018 | ||
Budget Rental - exterior lighting 87 NITS |