PREL201809649
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Final Inspection | Pending | |||
Corrections:
Miscellaneous/Other
Outstanding
10/31/2018
Partial final complete- OK to occupy.
Display lighting to complete. Call for final when completed.
|
||||
Electrical Rough-in Inspection | Partial Pass | 9/20/2018 (8:00 - 10:00) | 9/20/2018 | 09/20/2018 |
Corrections:
Miscellaneous/Other
Comment Only
09/20/2018
Wall RI, above ceiling at hard lid RI OK
|
||||
Electrical Rough-in Inspection | Passed w/ Conditions | 10/17/2018 (12:30 - 2:30) | 10/17/2018 | 10/17/2018 |
Corrections:
Miscellaneous/Other
Outstanding
10/17/2018
Power supplies for LED lighting must be NRTL listed and labeled for the purpose.
Drivers must be NRTL Class 2
|
||||
Miscellaneous/Other
Comment Only
10/17/2018
Above drop ceiling OK
|
||||
Electrical Final Inspection | Partial Pass | 10/30/2018 (8:00 - 10:00) | 10/30/2018 (AM) | 10/30/2018 |
Corrections:
Miscellaneous/Other
Comment Only
10/30/2018
Site visit OK.
Sign OK
EM not working correctly. Call for inspection prior to store opening.
GFCI for water fountain to be readily accessible.
Install all arc flash warning labels.
Display lighting not NRTL- replacement or disconnect.
|
||||
Miscellaneous/Other
Outstanding
10/31/2018
Partial final approved- all that remains is display lighting. Call for final when completed.
|
||||
Electrical Final Inspection | Partial Pass | 10/31/2018 (10:00 - 12:00) | 10/31/2018 (AM) | 10/31/2018 |
Corrections:
Miscellaneous/Other
Carried Forward
10/31/2018
Partial final complete- OK to occupy.
Display lighting to complete. Call for final when completed.
|