Permit Application Status

PREL201810854


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL201810854
Electrical
Finaled
ALIDADE CEDAR I LLC
Repair/Replace
Add 5 outlets at showroom stairs, ADDED 10/10/18: and remove NM cable from ceiling and walls.
09/14/2018
09/17/2018
04/13/2019
10/15/2018

Locations

Permits

Permit Number: PREL201810854

Electrical
Finaled
09/17/2018
04/13/2019

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 9/18/2018 (8:00 - 10:00) 9/18/2018 09/18/2018
Corrections:


Miscellaneous/Other
Outstanding
09/18/2018
NM cable in ceilings to be removed and completed in an approved wiring method.

Miscellaneous/Other
Comment Only
09/18/2018
Outlets in stair area only RI - ok Tried contractor and voicemail box was full.

Electrical Rough-in Inspection Passed 10/11/2018 (10:00 - 12:00) 10/11/2018 10/11/2018
Corrections:


Miscellaneous/Other
Comment Only
10/11/2018
NM cable removed from ceiling and walls . RI - ok

Electrical Final Inspection Passed 10/15/2018
Corrections:


Miscellaneous/Other
Comment Only
10/15/2018
All NM cable appears to be removed from space. Final - ok