Summary

PREL201811184
Electrical
Finaled
OXBORO BLOOMINGTON RETAIL CENTER LLC
Repair/Replace
Tanning beds and basic power for tennant space. Will also power the exterior sign.
09/20/2018
10/22/2018
09/16/2019
03/20/2019

Locations

Permits

Permit Number: PREL201811184

Electrical
Finaled

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Passed 10/22/2018 (2:30 - 3:30) 10/22/2018 10/22/2018
Corrections:


Miscellaneous/Other
Comment Only
10/22/2018
RI walls only- ok

Electrical Final Inspection Partial Pass 12/20/2018 (2:30 - 3:30) 12/20/2018 (PM) 12/20/2018
Corrections:


Miscellaneous/Other
Carried Forward
12/20/2018
LED drivers not labeled class 2. Class 2 wiring cannot be used to wire the strip LED. Need to use class 2 listed power supply.

Miscellaneous/Other
Carried Forward
12/20/2018
LED driver above ceiling cord and plug connected. Cannot be above drop ceiling.

Miscellaneous/Other
Carried Forward
12/20/2018
No NRTL listings on Hyperthermic tub/ Cocoon.

Miscellaneous/Other
Carried Forward
12/20/2018
Float tank will need evaluation. Will talk with building and environmental health.

Miscellaneous/Other
Carried Forward
12/20/2018
New panels need available fault current labels and orange arc flash labels .

Electrical Final Inspection Partial Pass 1/2/2019 (10:00 - 12:00) 1/2/2019 (AM) 01/02/2019
Corrections:


Miscellaneous/Other
Resolved
01/02/2019
LED drivers not labeled class 2. Class 2 wiring cannot be used to wire the strip LED. Need to use class 2 listed power supply.

Miscellaneous/Other
Resolved
01/02/2019
LED driver above ceiling cord and plug connected. Cannot be above drop ceiling.

Miscellaneous/Other
Carried Forward
01/02/2019
No NRTL listings on Hyperthermic tub/ Cocoon.

Miscellaneous/Other
Carried Forward
01/02/2019
Float tank will need evaluation. Will talk with building and environmental health.

Miscellaneous/Other
Carried Forward
01/02/2019
New panels need available fault current labels and orange arc flash labels .

Miscellaneous/Other
Comment Only
01/02/2019
New cocoon to be delivered on Friday. Schedule stop for NRTL check. TCO - ok

Electrical Final Inspection Partial Pass 1/10/2019 (8:00 - 10:00) 1/10/2019 (AM) 01/10/2019
Corrections:


Miscellaneous/Other
Resolved
01/10/2019
No NRTL listings on Hyperthermic tub/ Cocoon.

Miscellaneous/Other
Carried Forward
01/10/2019
Float tank will need evaluation. Will talk with building and environmental health.

Miscellaneous/Other
Carried Forward
01/10/2019
New panels need available fault current labels and orange arc flash labels .

Miscellaneous/Other
Comment Only
01/10/2019
Cocoon listing- ok Released for use.

Lighting Inspection Passed 01/23/2019
Totally Tan 207 NITS
Electrical Final Inspection Partial Pass 2/11/2019 (10:00 - 12:00) 2/11/2019 (AM) 02/11/2019
Corrections:


Miscellaneous/Other
Carried Forward
02/11/2019
Float tank will need evaluation. Will talk with building and environmental health.

Miscellaneous/Other
Resolved
02/11/2019
New panels need available fault current labels and orange arc flash labels .

Miscellaneous/Other
Comment Only
02/11/2019
Panel updates - ok

Electrical Final Inspection Passed 3/20/2019 (10:00 - 12:00) 3/20/2019 (AM) 03/20/2019
Corrections:


Miscellaneous/Other
Resolved
03/20/2019
Float tank will need evaluation. Will talk with building and environmental health.

Miscellaneous/Other
Comment Only
03/20/2019
All issues resolved for electrical approval with sensory tank. - ok Licensing for public use needed from others.