PREL201811184
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Passed | 10/22/2018 (2:30 - 3:30) | 10/22/2018 | 10/22/2018 |
Corrections:
Miscellaneous/Other
Comment Only
10/22/2018
RI walls only- ok
|
||||
Electrical Final Inspection | Partial Pass | 12/20/2018 (2:30 - 3:30) | 12/20/2018 (PM) | 12/20/2018 |
Corrections:
Miscellaneous/Other
Carried Forward
12/20/2018
LED drivers not labeled class 2. Class 2 wiring cannot be used to wire the strip LED. Need to use class 2 listed power supply.
|
||||
Miscellaneous/Other
Carried Forward
12/20/2018
LED driver above ceiling cord and plug connected. Cannot be above drop ceiling.
|
||||
Miscellaneous/Other
Carried Forward
12/20/2018
No NRTL listings on Hyperthermic tub/ Cocoon.
|
||||
Miscellaneous/Other
Carried Forward
12/20/2018
Float tank will need evaluation. Will talk with building and environmental health.
|
||||
Miscellaneous/Other
Carried Forward
12/20/2018
New panels need available fault current labels and orange arc flash labels .
|
||||
Electrical Final Inspection | Partial Pass | 1/2/2019 (10:00 - 12:00) | 1/2/2019 (AM) | 01/02/2019 |
Corrections:
Miscellaneous/Other
Resolved
01/02/2019
LED drivers not labeled class 2. Class 2 wiring cannot be used to wire the strip LED. Need to use class 2 listed power supply.
|
||||
Miscellaneous/Other
Resolved
01/02/2019
LED driver above ceiling cord and plug connected. Cannot be above drop ceiling.
|
||||
Miscellaneous/Other
Carried Forward
01/02/2019
No NRTL listings on Hyperthermic tub/ Cocoon.
|
||||
Miscellaneous/Other
Carried Forward
01/02/2019
Float tank will need evaluation. Will talk with building and environmental health.
|
||||
Miscellaneous/Other
Carried Forward
01/02/2019
New panels need available fault current labels and orange arc flash labels .
|
||||
Miscellaneous/Other
Comment Only
01/02/2019
New cocoon to be delivered on Friday. Schedule stop for NRTL check.
TCO - ok
|
||||
Electrical Final Inspection | Partial Pass | 1/10/2019 (8:00 - 10:00) | 1/10/2019 (AM) | 01/10/2019 |
Corrections:
Miscellaneous/Other
Resolved
01/10/2019
No NRTL listings on Hyperthermic tub/ Cocoon.
|
||||
Miscellaneous/Other
Carried Forward
01/10/2019
Float tank will need evaluation. Will talk with building and environmental health.
|
||||
Miscellaneous/Other
Carried Forward
01/10/2019
New panels need available fault current labels and orange arc flash labels .
|
||||
Miscellaneous/Other
Comment Only
01/10/2019
Cocoon listing- ok
Released for use.
|
||||
Lighting Inspection | Passed | 01/23/2019 | ||
Totally Tan 207 NITS | ||||
Electrical Final Inspection | Partial Pass | 2/11/2019 (10:00 - 12:00) | 2/11/2019 (AM) | 02/11/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
02/11/2019
Float tank will need evaluation. Will talk with building and environmental health.
|
||||
Miscellaneous/Other
Resolved
02/11/2019
New panels need available fault current labels and orange arc flash labels .
|
||||
Miscellaneous/Other
Comment Only
02/11/2019
Panel updates - ok
|
||||
Electrical Final Inspection | Passed | 3/20/2019 (10:00 - 12:00) | 3/20/2019 (AM) | 03/20/2019 |
Corrections:
Miscellaneous/Other
Resolved
03/20/2019
Float tank will need evaluation. Will talk with building and environmental health.
|
||||
Miscellaneous/Other
Comment Only
03/20/2019
All issues resolved for electrical approval with sensory tank. - ok
Licensing for public use needed from others.
|