Summary

PREL201811781
Electrical
Finaled
MSP BLOOMINGTON LLC
New
Wire new building
10/02/2018
01/23/2019
03/25/2020

Locations

Permits

Permit Number: PREL201811781

Electrical
Finaled
01/23/2019
03/25/2020

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 1/29/2019 (10:00 - 12:00) 1/29/2019 (AM) 01/29/2019
Corrections:


Miscellaneous/Other
Comment Only
01/29/2019
Wall RI- OK

Electrical Rough-in Inspection Partial Pass 3/11/2019 (12:30 - 2:30) 3/11/2019 (PM) 03/11/2019
Corrections:


Miscellaneous/Other
Comment Only
03/11/2019
Service inspection. Bond at CT cabinet and email photo. Grounding is not complete. OK to release to Xcel. 1200 AMP - 3 phase 120/208 volt commercial service. Maintain clear and unobstructed exiting from electrical rooms.

Electrical Rough-in Inspection Partial Pass 5/2/2019 (8:00 - 10:00) 5/2/2019 (AM) 05/02/2019
Corrections:


Miscellaneous/Other
Comment Only
05/02/2019
RI OK At escape room #4

Electrical Rough-in Inspection Partial Pass 5/14/2019 (12:30 - 2:30) 5/14/2019 (PM) 05/14/2019
Corrections:


Miscellaneous/Other
Comment Only
05/14/2019
Above ceiling at kitchen, bathrooms, and drop ceiling areas

Electrical Rough-in Inspection Passed 5/29/2019 (10:00 - 12:00) 5/29/2019 (AM) 05/29/2019
Corrections:


Miscellaneous/Other
Comment Only
05/29/2019
Above ceiling at escape room OK

Progress Inspection Partial Pass 6/10/2019 (8:00 - 10:00) 6/10/2019 (AM) 06/10/2019
Corrections:


Miscellaneous/Other
Comment Only
06/10/2019
Progress inspection- elevator equipment OK.

Miscellaneous/Other
Comment Only
06/10/2019
Progress inspection- rooftop equipment OK

Miscellaneous/Other
Carried Forward
06/10/2019
Verify available fault current: RTU equipment has a 5 K SCCR ratings. Elevator equipment has a 10 K SCCR rating.

Electrical Final Inspection Partial Pass 6/18/2019 (10:00 - 12:00) 6/18/2019 (AM) 06/18/2019
Corrections:


Miscellaneous/Other
Carried Forward
07/17/2019
Verify available fault current: RTU equipment has a 5 K SCCR ratings. Elevator equipment has a 10 K SCCR rating.

Miscellaneous/Other
Comment Only
06/18/2019
Progress inspection- plug checks at upper level.

Electrical Final Inspection Failed 7/17/2019 (10:00 - 12:00) 7/17/2019 (AM) 07/17/2019
Corrections:


Miscellaneous/Other
Comment Only
07/17/2019
Receptacle checks at bar OK. Life safety test for lighting OK See list for unresolved items:

Miscellaneous/Other
Comment Only
08/07/2019
For final inspection: see email correspondence. 1. Provide available fault current at service and documentation for any series rated panels. 2. Energy code compliance documentation. 3. Independent third party evaluations. 4. As built plans. Laser tag area not complete, main level kitchen not complete.

Miscellaneous/Other
Comment Only
08/07/2019
OK to occupy and use space- partial pass for final inspection.

Electrical Final Inspection Partial Pass 8/7/2019 (10:00 - 12:00) 8/7/2019 (AM) 08/07/2019
Corrections:


Miscellaneous/Other
Carried Forward
08/07/2019
Verify available fault current: RTU equipment has a 5 K SCCR ratings. Elevator equipment has a 10 K SCCR rating.

Miscellaneous/Other
Comment Only
08/07/2019
OK to occupy and use space. Partial pass of electrical final inspection.

Miscellaneous/Other
Carried Forward
08/07/2019
Verify listing of black light luminaries and power supplies at vest charging stations at laser tag area.

Miscellaneous/Other
Carried Forward
08/07/2019
Review of submittals by AHJ. Clarification needed at available fault current.

Miscellaneous/Other
Carried Forward
08/07/2019
Signs are not complete.

Electrical Final Inspection VOID 09/27/2019
Corrections:


Miscellaneous/Other
Resolved
09/27/2019
Verify available fault current: RTU equipment has a 5 K SCCR ratings. Elevator equipment has a 10 K SCCR rating.

Miscellaneous/Other
Resolved
09/27/2019
Verify listing of black light luminaries and power supplies at vest charging stations at laser tag area.

Miscellaneous/Other
Resolved
09/27/2019
Review of submittals by AHJ. Clarification needed at available fault current.

Miscellaneous/Other
Resolved
09/27/2019
Signs are not complete.

Electrical Final Inspection Passed 09/27/2019
12/23/2019: Finaled the information - was stuck in issued. Vandewege Meredith 12/23/2019 3:02 PM