PREL201812939
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 11/13/2018 (8:00 - 10:00) | 11/13/2018 (AM) | 11/13/2018 |
Corrections:
Miscellaneous/Other
Comment Only
11/13/2018
Walk RI- ok
|
||||
Electrical Rough-in Inspection | Passed w/ Conditions | 12/3/2018 (10:00 - 12:00) | 12/3/2018 (AM) | 12/03/2018 |
Corrections:
Miscellaneous/Other
Comment Only
12/03/2018
UG ok to cover provide pictures.
Panel location - ok provide adequate working space.
|
||||
Miscellaneous/Other
Comment Only
12/03/2018
Xformer to be installed from ceiling , review NEC 240.21 C for OCP locations.
|
||||
Electrical Final Inspection | Partial Pass | 12/18/2018 (12:30 - 2:30) | 12/18/2018 (PM) | 12/18/2018 |
Corrections:
Miscellaneous/Other
Comment Only
12/18/2018
Kitchen area only.
GFCI for fridge in kitchen space, check for accessible to GFCI or CB.
|
||||
Electrical Rough-in Inspection | Partial Pass | 1/10/2019 (10:00 - 12:00) | 1/10/2019 (AM) | 01/10/2019 |
Corrections:
Miscellaneous/Other
Comment Only
01/10/2019
Wall RI center of store high outlets- ok
|
||||
Electrical Final Inspection | Failed | 3/12/2019 (12:30 - 2:30) | 3/12/2019 (PM) | 03/12/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
03/12/2019
Multiwire circuits require handle ties.
|
||||
Miscellaneous/Other
Carried Forward
03/12/2019
Double wires under lug on xformer need to be changed
|
||||
Miscellaneous/Other
Carried Forward
03/12/2019
Verify xformer sizing and OCP.
|
||||
Electrical Final Inspection | Passed | 03/15/2019 | ||
Corrections:
Miscellaneous/Other
Resolved
03/15/2019
Multiwire circuits require handle ties.
|
||||
Miscellaneous/Other
Resolved
03/15/2019
Double wires under lug on xformer need to be changed
|
||||
Miscellaneous/Other
Resolved
03/15/2019
Verify xformer sizing and OCP.
|
||||
Miscellaneous/Other
Comment Only
03/15/2019
Xformer locking means - ok
All other issues resolved.
|