Summary

PREL201812939
Electrical
Finaled
KRAUS-ANDERSON INC
Alteration/Remodel
Add 200a service and receptacles and relocate misc lights
10/18/2018
11/07/2018
09/11/2019
03/15/2019

Locations

Permits

Permit Number: PREL201812939

Electrical
Finaled

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 11/13/2018 (8:00 - 10:00) 11/13/2018 (AM) 11/13/2018
Corrections:


Miscellaneous/Other
Comment Only
11/13/2018
Walk RI- ok

Electrical Rough-in Inspection Passed w/ Conditions 12/3/2018 (10:00 - 12:00) 12/3/2018 (AM) 12/03/2018
Corrections:


Miscellaneous/Other
Comment Only
12/03/2018
UG ok to cover provide pictures. Panel location - ok provide adequate working space.

Miscellaneous/Other
Comment Only
12/03/2018
Xformer to be installed from ceiling , review NEC 240.21 C for OCP locations.

Electrical Final Inspection Partial Pass 12/18/2018 (12:30 - 2:30) 12/18/2018 (PM) 12/18/2018
Corrections:


Miscellaneous/Other
Comment Only
12/18/2018
Kitchen area only. GFCI for fridge in kitchen space, check for accessible to GFCI or CB.

Electrical Rough-in Inspection Partial Pass 1/10/2019 (10:00 - 12:00) 1/10/2019 (AM) 01/10/2019
Corrections:


Miscellaneous/Other
Comment Only
01/10/2019
Wall RI center of store high outlets- ok

Electrical Final Inspection Failed 3/12/2019 (12:30 - 2:30) 3/12/2019 (PM) 03/12/2019
Corrections:


Miscellaneous/Other
Carried Forward
03/12/2019
Multiwire circuits require handle ties.

Miscellaneous/Other
Carried Forward
03/12/2019
Double wires under lug on xformer need to be changed

Miscellaneous/Other
Carried Forward
03/12/2019
Verify xformer sizing and OCP.

Electrical Final Inspection Passed 03/15/2019
Corrections:


Miscellaneous/Other
Resolved
03/15/2019
Multiwire circuits require handle ties.

Miscellaneous/Other
Resolved
03/15/2019
Double wires under lug on xformer need to be changed

Miscellaneous/Other
Resolved
03/15/2019
Verify xformer sizing and OCP.

Miscellaneous/Other
Comment Only
03/15/2019
Xformer locking means - ok All other issues resolved.