PREL201813152
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Final Inspection | Pending | |||
Corrections:
Miscellaneous/Other
Outstanding
11/19/2018
Feeds to RTU’s need replacement. All exposed / existing seal tight connections to building severely deteriorated.
|
||||
Miscellaneous/Other
Outstanding
11/19/2018
SCCR rating of RTU’s 5k. Verify and label available SCCR at units, per conditions on permit
|
||||
Electrical Final Inspection | Failed | 11/19/2018 (10:00 - 12:00) | 11/19/2018 (AM) | 11/19/2018 |
Corrections:
Miscellaneous/Other
Carried Forward
11/19/2018
Feeds to RTU’s need replacement. All exposed / existing seal tight connections to building severely deteriorated.
|
||||
Miscellaneous/Other
Carried Forward
11/19/2018
SCCR rating of RTU’s 5k. Verify and label available SCCR at units, per conditions on permit
|