PREL201813597
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Final Inspection | Pending | |||
|
Corrections:
Miscellaneous/Other
Outstanding
11/20/2018
Verify available fault current at service.
Any subpanel may require series ratings.
Call for reinspection.
|
||||
| Electrical Final Inspection | Failed | 11/19/2018 (10:00 - 12:00) | 11/19/2018 (AM) | 11/19/2018 |
|
Corrections:
Miscellaneous/Other
Carried Forward
11/19/2018
Service requires a grounded conductor brought to service disconnect and GEC connection brought to the grounded conductor.
|
||||
|
Miscellaneous/Other
Carried Forward
11/19/2018
Verify available fault current at service.
Any subpanel may require series ratings.
Call for reinspection.
|
||||
| Electrical Final Inspection | Partial Pass | 11/20/2018 (Afternoon) | 11/20/2018 (PM) | 11/20/2018 |
|
Corrections:
Miscellaneous/Other
Comment Only
11/20/2018
Service requires a grounded conductor brought to service disconnect and GEC connection brought to the grounded conductor.
|
||||
|
Miscellaneous/Other
Carried Forward
11/20/2018
Verify available fault current at service.
Any subpanel may require series ratings.
Call for reinspection.
|
||||
|
Miscellaneous/Other
Comment Only
11/20/2018
Released to Xcel. Permit kept open for subsequent inspections.
|
||||