Summary

PREL201813597
Electrical
Expired
101 AMERICAN BLVD W LLC
Alteration/Remodel
Temp service
10/29/2018
10/30/2018
05/19/2019

Locations

Permits

Permit Number: PREL201813597

Electrical
Expired
10/30/2018
05/19/2019

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Pending
Corrections:


Miscellaneous/Other
Outstanding
11/20/2018
Verify available fault current at service. Any subpanel may require series ratings. Call for reinspection.

Electrical Final Inspection Failed 11/19/2018 (10:00 - 12:00) 11/19/2018 (AM) 11/19/2018
Corrections:


Miscellaneous/Other
Carried Forward
11/19/2018
Service requires a grounded conductor brought to service disconnect and GEC connection brought to the grounded conductor.

Miscellaneous/Other
Carried Forward
11/19/2018
Verify available fault current at service. Any subpanel may require series ratings. Call for reinspection.

Electrical Final Inspection Partial Pass 11/20/2018 (Afternoon) 11/20/2018 (PM) 11/20/2018
Corrections:


Miscellaneous/Other
Comment Only
11/20/2018
Service requires a grounded conductor brought to service disconnect and GEC connection brought to the grounded conductor.

Miscellaneous/Other
Carried Forward
11/20/2018
Verify available fault current at service. Any subpanel may require series ratings. Call for reinspection.

Miscellaneous/Other
Comment Only
11/20/2018
Released to Xcel. Permit kept open for subsequent inspections.