PREL201815044
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 12/14/2018 (12:30 - 2:30) | 12/14/2018 (PM) | 12/14/2018 |
Corrections:
Miscellaneous/Other
Comment Only
12/14/2018
RI of walls for closets. Maintain proper clearance to luminarie located in closet, per NEC 410
|
||||
Miscellaneous/Other
Carried Forward
12/14/2018
Repair/ replace at door frame lighting switch-
Use of the door frame as a raceway and box.
Repair /replace to code.
|
||||
Miscellaneous/Other
Comment Only
12/14/2018
Provide GFCI protection receptacle outlet per 2017 NEC is required- existing must properly function.
|
||||
Miscellaneous/Other
Comment Only
12/14/2018
Verbal to general contractor- all electrical installations must be made by a MN State licensed contractor only. Fire alarm and temperature control wiring requires permit and inspection.
|
||||
Electrical Rough-in Inspection | Partial Pass | 12/19/2018 (10:00 - 12:00) | 12/19/2018 (AM) | 12/19/2018 |
Corrections:
Miscellaneous/Other
Comment Only
12/19/2018
Repair/ replace at door frame lighting switch-
Use of the door frame as a raceway and box.
Repair /replace to code.
|
||||
Miscellaneous/Other
Comment Only
12/19/2018
Site visit Ok for 2nd floor- remodel LED luminaries OK- spot check at subsequent inspections. Demolish old wiring to door frame switch locations.
|
||||
Electrical Rough-in Inspection | Failed | 12/21/2018 (8:00 - 10:00) | 12/21/2018 (AM) | 12/21/2018 |
Corrections:
Miscellaneous/Other
Carried Forward
12/21/2018
Violation of NEC 800.24 - existing communications cable improperly installed.
Install per recognized standards. Cable installed under carpet or behind base not permitted.
|
||||
Electrical Rough-in Inspection | Partial Pass | 12/21/2018 | ||
Corrections:
Miscellaneous/Other
Carried Forward
12/21/2018
Violation of NEC 800.24 - existing communications cable improperly installed.
Install per recognized standards. Cable installed under carpet or behind base not permitted.
|
||||
Miscellaneous/Other
Comment Only
12/21/2018
Wall outlet fished in at closet wall in multiple units- visual OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 1/7/2019 (10:00 - 12:00) | 1/7/2019 (AM) | 01/07/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
01/07/2019
Violation of NEC 800.24 - existing communications cable improperly installed.
Install per recognized standards. Cable installed under carpet or behind base not permitted.
|
||||
Miscellaneous/Other
Comment Only
01/07/2019
Installation of flex and box at door frames- OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 1/16/2019 (12:30 - 2:30) | 1/16/2019 (PM) | 01/16/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
01/16/2019
Violation of NEC 800.24 - existing communications cable improperly installed.
Install per recognized standards. Cable installed under carpet or behind base not permitted.
|
||||
Miscellaneous/Other
Comment Only
01/16/2019
NRTL labels for mirror lighting and sconces OK.
Walk thru units for pre final on second floor OK
|
||||
Electrical Rough-in Inspection | Not Ready | 1/17/2019 (12:30 - 2:30) | 1/17/2019 (PM) | 01/17/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
01/17/2019
Violation of NEC 800.24 - existing communications cable improperly installed.
Install per recognized standards. Cable installed under carpet or behind base not permitted.
|
||||
Electrical Final Inspection | Partial Pass | 2/5/2019 (12:30 - 2:30) | 2/5/2019 (PM) | 02/05/2019 |
Corrections:
Miscellaneous/Other
Comment Only
02/05/2019
RI OK at 2 units.
Final OK at all except corner units and AADA units and at RI units 215,216.
|
||||
Electrical Rough-in Inspection | Partial Pass | 3/5/2019 (2:30 - 3:30) | 3/5/2019 (PM) | 03/05/2019 |
Corrections:
Miscellaneous/Other
Resolved
03/05/2019
Violation of NEC 800.24 - existing communications cable improperly installed.
Install per recognized standards. Cable installed under carpet or behind base not permitted.
|
||||
Miscellaneous/Other
Comment Only
03/05/2019
Final ok at units 204 and 231
|
||||
Electrical Final Inspection | Passed | 8/23/2019 (12:30 - 2:30) | 8/23/2019 (PM) | 08/23/2019 |
Electrical Rough-in Inspection | VOID | 12/31/2019 |