Summary

PREL201815241
Electrical
Finaled
MOAC LAND HOLDINGS LLC
Alteration/Repair/Replace
New buildtout of retail space.
12/14/2018
01/04/2019
11/14/2020
05/18/2020

Locations

Permits

Permit Number: PREL201815241

Electrical
Finaled
01/04/2019
11/14/2020

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 1/16/2019 (8:00 - 10:00) 1/16/2019 (AM) 01/16/2019
Corrections:


Miscellaneous/Other
Comment Only
01/16/2019
RI OK at 2nd floor prep kitchen. Note there are two separate spaces associated with this permit. The larger space on 3rd floor and a smaller prep space on 2nd floor.

Electrical Rough-in Inspection Partial Pass 1/25/2019 (8:00 - 10:00) 1/25/2019 (AM) 01/25/2019
Corrections:


Miscellaneous/Other
Comment Only
01/25/2019
Wall RI OK at 3rd floor

Electrical Rough-in Inspection Partial Pass 1/29/2019 (8:00 - 10:00) 1/29/2019 (AM) 01/29/2019
Corrections:


Miscellaneous/Other
Comment Only
01/29/2019
Half height prep wall RI -OK

Electrical Rough-in Inspection Partial Pass 8/26/2019 (12:30 - 2:30) 8/26/2019 (PM) 08/26/2019
Corrections:


Miscellaneous/Other
Comment Only
08/26/2019
Wall RI OK at bar walls

Electrical Rough-in Inspection Partial Pass 9/6/2019 (8:00 - 10:00) 9/6/2019 (AM) 09/06/2019
Corrections:


Miscellaneous/Other
Comment Only
09/06/2019
Front of house ceiling RI- OK Wall RI OK complete

Electrical Rough-in Inspection Partial Pass 11/4/2019 (8:00 - 10:00) 11/4/2019 (AM) 11/04/2019
Corrections:


Miscellaneous/Other
Comment Only
11/04/2019
There are two separate spaces under this permit. Space 255 remote kitchen area final OK except GFCI required for 3 phase receptacle

Electrical Final Inspection Partial Pass 11/6/2019 (10:00 - 12:00) 11/6/2019 (AM) 11/06/2019
Corrections:


Miscellaneous/Other
Comment Only
11/06/2019
Egress lighting OK

Miscellaneous/Other
Resolved
11/07/2019
Provide disconnect means lockable in the off position for all kitchen equipment not cord and plug connected

Miscellaneous/Other
Comment Only
11/06/2019
Listing of sign at storefront OK

Miscellaneous/Other
Resolved
11/07/2019
Install protection of transformer secondary conductors to code.

Electrical Final Inspection Partial Pass 11/7/2019 (10:00 - 12:00) 11/7/2019 (AM) 11/07/2019
Corrections:


Miscellaneous/Other
Comment Only
11/07/2019
Partial pass. Corrections made. Complete all installations and call for final

Miscellaneous/Other
Comment Only
11/07/2019
Inspection note- unable to obtain roof access.

Miscellaneous/Other
Outstanding
11/13/2019
Inspection note- secondary connections for neon signs is electrical work and must be performed by a MN State licensed contractor

Electrical Rough-in Inspection Partial Pass 11/13/2019 (10:00 - 12:00) 11/13/2019 (AM) 11/13/2019
Corrections:


Miscellaneous/Other
Carried Forward
11/13/2019
Neon work not complete. All other electrical inspection items OK- partial final except as noted. Contractor performing neon required permit and inspection

Electrical Final Inspection Passed 05/18/2020
Corrections:


Miscellaneous/Other
Resolved
05/18/2020
Inspection note- secondary connections for neon signs is electrical work and must be performed by a MN State licensed contractor