PREL201815452


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL201815452
Electrical
Finaled
SEWELL, MELINDA
Alteration/Repair/Replace
Reconnect furnace; whip for AC
12/21/2018
12/26/2018
10/13/2019
04/16/2019

Locations

Permits

Permit Number: PREL201815452

Electrical
Finaled
12/26/2018
10/13/2019

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Failed 1/18/2019 (8:00 - 10:00) 1/18/2019 (AM) 01/18/2019
Corrections:


Miscellaneous/Other
Resolved
04/16/2019
3/4 EMT conduit is not terminated or mechanically connected to air conditioning disconnect. Repair or replace to code - provide mechanical and electrical continuity.

Miscellaneous/Other
Resolved
04/16/2019
Remove limited energy- general purpose "bell wire" from same raceway as power. Install "low voltage" wiring to contactor per NEC requirements.

Electrical Final Inspection Passed 04/16/2019
Corrections:


Miscellaneous/Other
Resolved
04/16/2019
3/4 EMT conduit is not terminated or mechanically connected to air conditioning disconnect. Repair or replace to code - provide mechanical and electrical continuity.

Miscellaneous/Other
Resolved
04/16/2019
Remove limited energy- general purpose "bell wire" from same raceway as power. Install "low voltage" wiring to contactor per NEC requirements.

Miscellaneous/Other
Comment Only
04/16/2019
Photos received of corrections