PREL201815452
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Final Inspection | Failed | 1/18/2019 (8:00 - 10:00) | 1/18/2019 (AM) | 01/18/2019 |
|
Corrections:
Miscellaneous/Other
Resolved
04/16/2019
3/4 EMT conduit is not terminated or mechanically connected to air conditioning disconnect. Repair or replace to code - provide mechanical and electrical continuity.
|
||||
|
Miscellaneous/Other
Resolved
04/16/2019
Remove limited energy- general purpose "bell wire" from same raceway as power. Install "low voltage" wiring to contactor per NEC requirements.
|
||||
| Electrical Final Inspection | Passed | 04/16/2019 | ||
|
Corrections:
Miscellaneous/Other
Resolved
04/16/2019
3/4 EMT conduit is not terminated or mechanically connected to air conditioning disconnect. Repair or replace to code - provide mechanical and electrical continuity.
|
||||
|
Miscellaneous/Other
Resolved
04/16/2019
Remove limited energy- general purpose "bell wire" from same raceway as power. Install "low voltage" wiring to contactor per NEC requirements.
|
||||
|
Miscellaneous/Other
Comment Only
04/16/2019
Photos received of corrections
|
||||