PREL201900513
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 2/6/2019 (8:00 - 10:00) | 2/6/2019 (AM) | 02/06/2019 |
Corrections:
Miscellaneous/Other
Comment Only
02/06/2019
Wall RI OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 2/13/2019 (2:30 - 3:30) | 2/13/2019 (PM) | 02/13/2019 |
Corrections:
Miscellaneous/Other
Comment Only
02/13/2019
RI OK at hard lid at dressing rooms.
|
||||
Electrical Final Inspection | Failed | 3/27/2019 (8:00 - 10:00) | 3/27/2019 (AM) | 03/27/2019 |
Corrections:
Miscellaneous/Other
Resolved
04/01/2019
Lock on EM breaker at panel.
|
||||
Miscellaneous/Other
Resolved
04/01/2019
No listing label visible at fitting room sign.
|
||||
Miscellaneous/Other
Resolved
04/01/2019
Verify access into 1900 box at cabinet behind cash wrap.
|
||||
Miscellaneous/Other
Resolved
04/01/2019
Complete all installations and provide access for any all signs. Disconnect means and NRTL listing/ labeling required.
|
||||
Miscellaneous/Other
Resolved
04/01/2019
Verify available fault current at lighting control cabinet. SCCR rating of 5 K per nameplate.
|
||||
Miscellaneous/Other
Resolved
04/01/2019
Provide pics of transformer connections.
Verify bond from electrode system to metal water piping in the area served.
Email to Tmiller@bloomingtonmn.gov
|
||||
Electrical Final Inspection | Passed | 4/1/2019 (8:00 - 10:00) | 4/1/2019 (AM) | 04/01/2019 |