Summary

PREL201901993
Electrical
Finaled
G&I VIII WF PLAZA LLC
Other
Remodel - 77 lights, 15 sensors, 20 receptacles, 3 sets of furniture
03/08/2019
03/08/2019
10/29/2019
05/02/2019

Locations

Permits

Permit Number: PREL201901993

Electrical
Finaled
03/08/2019
10/29/2019

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 3/14/2019 (8:00 - 10:00) 3/14/2019 (AM) 03/14/2019
Corrections:


Miscellaneous/Other
Comment Only
03/14/2019
Wall RI only - ok FA and temp control permits required.

Miscellaneous/Other
Carried Forward
03/14/2019
New heat pump above ceiling with condensate pump. Check at above ceiling RI.

Electrical Rough-in Inspection Passed 4/8/2019 (2:30 - 3:30) 4/8/2019 (PM) 04/08/2019
Corrections:


Miscellaneous/Other
Comment Only
04/08/2019
New heat pump above ceiling with condensate pump. Check at above ceiling RI. Heat pump connected under permit, condensate pump removed .

Miscellaneous/Other
Comment Only
04/08/2019
Above ceiling - ok Need better marking of ceiling support wires.

Electrical Final Inspection Passed 5/2/2019 (8:00 - 3:30) 5/2/2019 (AM) 05/02/2019
Corrections:


Miscellaneous/Other
Comment Only
05/02/2019
Final- ok Verify plenum condensate pump when installed.