Permit Application Status

PREL201902078


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL201902078
Electrical
Finaled
BLOOMINGTON CENTRAL
Alteration/Repair/Replace
WIRE NEW SIGN
03/12/2019
03/19/2019
10/16/2019
04/19/2019

Locations

Permits

Permit Number: PREL201902078

Electrical
Finaled
03/19/2019
10/16/2019

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Lighting Inspection Passed 03/20/2019
Electrical Final Inspection Failed 3/21/2019 (12:30 - 2:30) 3/21/2019 (PM) 03/21/2019
Corrections:


Miscellaneous/Other
Carried Forward
03/21/2019
Unable to verify NRTL listing and labeling of sign. Unable to verify nameplate ratings. All signs must be NRTL listed and labeled- no field application of labels permitted. Verify listing with manufacturer and communicate locations to inspections.

Miscellaneous/Other
Carried Forward
03/21/2019
No marrkings for LED driver enclosure. Enclosures must be listed for purpose and for wet locations.

Miscellaneous/Other
Carried Forward
03/21/2019
Based on absence of labeling- verify if the drivers are listed specifically for sign use per NEC 600.24 Signs with multiple channel letters will have labels indicating ( for example ) 1 of 10, 2 of 10, 3 of 10...... Signs where the power supply is part of the listed sign will have NRTL label indicating 1 of 2 ( where the sign is a single listed unit ) and 2 of 2 on the power supply enclosure indicating that it is part of the sign.

Electrical Final Inspection Passed 4/19/2019 (10:00 - 12:00) 4/19/2019 (AM) 04/19/2019
Corrections:


Miscellaneous/Other
Resolved
04/19/2019
Unable to verify NRTL listing and labeling of sign. Unable to verify nameplate ratings. All signs must be NRTL listed and labeled- no field application of labels permitted. Verify listing with manufacturer and communicate locations to inspections.

Miscellaneous/Other
Resolved
04/19/2019
No marrkings for LED driver enclosure. Enclosures must be listed for purpose and for wet locations.

Miscellaneous/Other
Resolved
04/19/2019
Based on absence of labeling- verify if the drivers are listed specifically for sign use per NEC 600.24 Signs with multiple channel letters will have labels indicating ( for example ) 1 of 10, 2 of 10, 3 of 10...... Signs where the power supply is part of the listed sign will have NRTL label indicating 1 of 2 ( where the sign is a single listed unit ) and 2 of 2 on the power supply enclosure indicating that it is part of the sign.