PREL201902219
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Passed | 3/28/2019 (8:00 - 10:00) | 3/28/2019 (AM) | 03/28/2019 |
Corrections:
Miscellaneous/Other
Comment Only
03/28/2019
RI OK for walls and hard lid ceilings.
|
||||
Electrical Final Inspection | Failed | 4/23/2019 (12:30 - 2:30) | 4/23/2019 (PM) | 04/23/2019 |
Corrections:
Miscellaneous/Other
Resolved
05/28/2019
Verify NRTL listing of sign and sign power supply. Labels not visible
|
||||
Miscellaneous/Other
Resolved
05/28/2019
Cords above ceiling- return air space requires hard wiring of Refrigeration equipment
|
||||
Miscellaneous/Other
Resolved
05/28/2019
General contractor- notices and corrections:
Tenants camera installation- use of non-plenum cable in return air ceiling.
Repair requires electrical permit and inspection
Repair must be MN State licensed TS or electrical contractor.
|
||||
Miscellaneous/Other
Comment Only
05/28/2019
TO GC- tenant has tele-com equipment above return air ceiling- relocate or verify NRTL listing for plenum space
|
||||
Miscellaneous/Other
Comment Only
04/23/2019
OK to stock and train
|
||||
Electrical Final Inspection | Passed | 05/28/2019 | ||
Corrections:
Miscellaneous/Other
Resolved
05/28/2019
Verify NRTL listing of sign and sign power supply. Labels not visible
|
||||
Miscellaneous/Other
Resolved
05/28/2019
Cords above ceiling- return air space requires hard wiring of Refrigeration equipment
|
||||
Miscellaneous/Other
Resolved
05/28/2019
General contractor- notices and corrections:
Tenants camera installation- use of non-plenum cable in return air ceiling.
Repair requires electrical permit and inspection
Repair must be MN State licensed TS or electrical contractor.
|
||||
Miscellaneous/Other
Comment Only
05/28/2019
TO GC- tenant has tele-com equipment above return air ceiling- relocate or verify NRTL listing for plenum space
|