PREL201902472
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Failed | 4/1/2019 (8:00 - 3:30) | 4/1/2019 (AM) | 04/01/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
04/01/2019
Nameplate of new chiller requires MCA 720 and MOCP of 800. Feeders to chiller of only 2- 350kcmil per phase and changes to 2- 4/0 per phase .
No acces to view OCP for feeders.
|
||||
Electrical Final Inspection | Passed w/ Conditions | 6/27/2019 (7:00 - 8:00) | 6/27/2019 (AM) | 06/27/2019 |
Corrections:
Miscellaneous/Other
Comment Only
06/27/2019
Chillers require labeling
|
||||
Electrical Rough-in Inspection | Passed | 06/27/2019 | ||
Corrections:
Miscellaneous/Other
Resolved
06/27/2019
Nameplate of new chiller requires MCA 720 and MOCP of 800. Feeders to chiller of only 2- 350kcmil per phase and changes to 2- 4/0 per phase .
No acces to view OCP for feeders.
|
||||
Miscellaneous/Other
Comment Only
06/27/2019
Issues resolved new chillers in place.
|