Summary

PREL201902485
Electrical
Finaled
DELEGARD CURTIS/DUANE
Alteration/Repair/Replace
Change out (9) lights, add (2) 220v outlets. Add small panel for added circuits.
03/21/2019
03/22/2019
10/07/2019
04/10/2019

Locations

Permits

Permit Number: PREL201902485

Electrical
Finaled
03/22/2019
10/07/2019

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Failed 4/8/2019 (12:30 - 2:30) 4/8/2019 (PM) 04/08/2019
Corrections:


Miscellaneous/Other
Carried Forward
04/08/2019
Main panel Siemens brand, 60a feeder CB Eaton manufactures cannot be inter mixed.

Miscellaneous/Other
Carried Forward
04/08/2019
Subpanel Eaton brand, CB’s mixed one 30a Eaton ok, other 30 square D must be changed,, and two single pole 20a Siemens. CB must match manufactures panels.

Miscellaneous/Other
Carried Forward
04/08/2019
2- 20a circuits in subpanel need to have entire circuit grouped per NEC 300.3B. Neutrals cannot be left in other panel. These same circuits appear to be of a multi wire circuit. Which requires the entire circuit be grouped and CB must turn off all ungrounded conductors simultaneously per NEC 210.4

Electrical Final Inspection Passed 4/10/2019 (8:00 - 10:00) 4/10/2019 (AM) 04/10/2019
Corrections:


Miscellaneous/Other
Resolved
04/10/2019
Main panel Siemens brand, 60a feeder CB Eaton manufactures cannot be inter mixed.

Miscellaneous/Other
Resolved
04/10/2019
Subpanel Eaton brand, CB’s mixed one 30a Eaton ok, other 30 square D must be changed,, and two single pole 20a Siemens. CB must match manufactures panels.

Miscellaneous/Other
Resolved
04/10/2019
2- 20a circuits in subpanel need to have entire circuit grouped per NEC 300.3B. Neutrals cannot be left in other panel. These same circuits appear to be of a multi wire circuit. Which requires the entire circuit be grouped and CB must turn off all ungrounded conductors simultaneously per NEC 210.4

Miscellaneous/Other
Comment Only
04/10/2019
Issued resolved