PREL201902537
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 4/26/2019 (7:00 - 8:00) | 4/26/2019 (AM) | 04/26/2019 |
Corrections:
Miscellaneous/Other
Comment Only
04/26/2019
Wall RI only- ok
|
||||
Electrical Rough-in Inspection | Passed | 6/4/2019 (8:00 - 10:00) | 6/4/2019 (AM) | 06/04/2019 |
Corrections:
Miscellaneous/Other
Comment Only
06/04/2019
Above ceiling OK
|
||||
Electrical Final Inspection | Partial Pass | 06/04/2019 | ||
Corrections:
Miscellaneous/Other
Comment Only
06/04/2019
Partial pass-for final.
|
||||
Miscellaneous/Other
Carried Forward
06/04/2019
Partition furniture to complete- call for inspection when completed.
Verbal- arc flash warning labels for panel and install disconnect means for small fan at IT room.
|
||||
Electrical Final Inspection | Passed | 6/17/2019 (8:00 - 10:00) | 6/17/2019 (AM) | 06/17/2019 |
Corrections:
Miscellaneous/Other
Resolved
06/17/2019
Partition furniture to complete- call for inspection when completed.
Verbal- arc flash warning labels for panel and install disconnect means for small fan at IT room.
|
||||
Miscellaneous/Other
Comment Only
06/17/2019
All issues resolved. Labeling and disconnect- ok
|