PREL201903213
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Final Inspection | Failed | 4/30/2019 (10:00 - 12:00) | 4/30/2019 (AM) | 04/30/2019 |
|
Corrections:
Miscellaneous/Other
Carried Forward
04/30/2019
All conductors must be properly marked , orange high leg, if white is used as ungrounded must be marked appropriately.
|
||||
|
Miscellaneous/Other
Carried Forward
04/30/2019
EGC needed for sealtight if not under 6’ or used for vibration purposes.
|
||||
|
Miscellaneous/Other
Carried Forward
04/30/2019
Motor overload protection needed per 430.32 for motors over 1hp.
|
||||
|
Miscellaneous/Other
Comment Only
04/30/2019
Will need meet onsite for next inspection.
|
||||
| Electrical Final Inspection | Passed | 5/9/2019 (12:30 - 2:30) | 5/9/2019 (PM) | 05/09/2019 |
|
Corrections:
Miscellaneous/Other
Resolved
05/09/2019
All conductors must be properly marked , orange high leg, if white is used as ungrounded must be marked appropriately.
|
||||
|
Miscellaneous/Other
Resolved
05/09/2019
EGC needed for sealtight if not under 6’ or used for vibration purposes.
|
||||
|
Miscellaneous/Other
Resolved
05/09/2019
Motor overload protection needed per 430.32 for motors over 1hp.
|
||||
|
Miscellaneous/Other
Comment Only
05/10/2019
Contractor verified Overloads open all ungrounded conductors.
|
||||