PREL201903997
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 5/21/2019 (8:00 - 10:00) | 5/21/2019 (AM) | 05/21/2019 |
Corrections:
Miscellaneous/Other
Comment Only
05/21/2019
Wall RI OK, hard lid RI OK
|
||||
Electrical Rough-in Inspection | Passed w/ Conditions | 6/24/2019 (8:00 - 3:30) | 6/24/2019 (PM) | 06/24/2019 |
Corrections:
Miscellaneous/Other
Resolved
07/02/2019
Remove and replace non plenum cable being installed for cameras
|
||||
Miscellaneous/Other
Resolved
07/02/2019
Complete MC cable securing above hard lid - no to exceed 6 feet intervals - verbal
|
||||
Miscellaneous/Other
Comment Only
06/24/2019
Above ceiling RI OK except as noted
|
||||
Electrical Final Inspection | Passed | 7/2/2019 (8:00 - 10:00) | 7/2/2019 (AM) | 07/02/2019 |