PREL201904459
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 9/27/2019 (10:00 - 12:00) | 9/27/2019 (AM) | 09/27/2019 |
Corrections:
Miscellaneous/Other
Comment Only
09/27/2019
Trench Inspection- partial OK at conduits leading to switchgear.
Also PVC runs to floor boxes.
|
||||
Electrical Rough-in Inspection | Partial Pass | 10/10/2019 (12:30 - 2:30) | 10/10/2019 (PM) | 10/10/2019 |
Corrections:
Miscellaneous/Other
Comment Only
10/10/2019
UG at south side of the building OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 11/1/2019 (10:00 - 12:00) | 10/31/2019 | |
Corrections:
Miscellaneous/Other
Comment Only
10/31/2019
Visual Ok at exterior parking lot light bases
|
||||
Electrical Rough-in Inspection | Partial Pass | 11/27/2019 (8:00 - 10:00) | 11/27/2019 (AM) | 11/27/2019 |
Corrections:
Miscellaneous/Other
Comment Only
11/27/2019
Wall RI- at all drywall walls OK
|
||||
Electrical Rough-in Inspection | Partial Pass | 1/13/2020 (10:00 - 12:00) | 1/13/2020 (AM) | 01/13/2020 |
Corrections:
Miscellaneous/Other
Carried Forward
01/13/2020
Met onsite to discuss EM feeder, needs separation in jbox location.
|
||||
Lighting Inspection | Passed | 01/27/2020 | ||
Electrical Rough-in Inspection | Partial Pass | 2/19/2020 (12:30 - 2:30) | 2/19/2020 (PM) | 02/19/2020 |
Corrections:
Miscellaneous/Other
Carried Forward
02/19/2020
Met onsite to discuss EM feeder, needs separation in jbox location.
|
||||
Miscellaneous/Other
Comment Only
02/19/2020
RI OK- for above hard lid ceiling at dayroom area.
|
||||
Electrical Rough-in Inspection | Partial Pass | 3/17/2020 (10:00 - 12:00) | 3/17/2020 (AM) | 03/17/2020 |
Corrections:
Miscellaneous/Other
Comment Only
03/17/2020
Met onsite to discuss EM feeder, needs separation in jbox location.
|
||||
Miscellaneous/Other
Comment Only
03/17/2020
Above ceiling RI OK at first floor
|
||||
Electrical Rough-in Inspection | Partial Pass | 4/16/2020 (12:30 - 2:30) | 4/16/2020 (PM) | 04/17/2020 |
Corrections:
Miscellaneous/Other
Comment Only
04/17/2020
Met contractor on site-
1. 1200 AMP 3 phase- 120/208 volt service- OK
2. Generator- set listing OK.
Verbal: complete bond at CT cabinet.
Verbal: remove neutral bond at feeder distribution switchboard
Verbal: revise equipment grounding connection to metal enclosure- tap-con connection requires modification.
Verbal: maintain physical separation between normal and EM power wiring at gutter.
|
||||
Electrical Final Inspection | Partial Pass | 5/13/2020 (10:00 - 12:00) | 5/13/2020 (AM) | 05/15/2020 |
Corrections:
Miscellaneous/Other
Comment Only
05/15/2020
Part pass- see email dated 05/15/2020
|
||||
Electrical Rough-in Inspection | Partial Pass | 5/19/2020 (12:30 - 2:30) | 5/19/2020 (PM) | 05/20/2020 |
Corrections:
Miscellaneous/Other
Comment Only
05/20/2020
Partial Final OK. See list for remaining items.
|
||||
Miscellaneous/Other
Carried Forward
05/20/2020
1. Unlisted equipment for the chain hoist at the top of the training/hose tower. My understanding is the equipment has been electrically disconnected.
2. The available fault current at the elevator control equipment exceeds the SCCR rating.
3. The code required manual transfer switch – lacks annunciation when transferred out the “normal” position, lacks phase rotation documentation and arc flash warning labels. See NEC requirements.
4. Verification of the SCCR rating of the life-safety transfer switch. Each transfer switch has a factory SCCR rating that changes based on the OCP device protecting the feeder. There is information regarding the clearing time and SCCR rating on the transfer equipment.
5. The installation of exhaust hood for the commercial range is not yet installed.
|
||||
Electrical Rough-in Inspection | Passed | 06/17/2020 | ||
Corrections:
Miscellaneous/Other
Comment Only
06/17/2020
1. Unlisted equipment for the chain hoist at the top of the training/hose tower. My understanding is the equipment has been electrically disconnected.
2. The available fault current at the elevator control equipment exceeds the SCCR rating.
3. The code required manual transfer switch – lacks annunciation when transferred out the “normal” position, lacks phase rotation documentation and arc flash warning labels. See NEC requirements.
4. Verification of the SCCR rating of the life-safety transfer switch. Each transfer switch has a factory SCCR rating that changes based on the OCP device protecting the feeder. There is information regarding the clearing time and SCCR rating on the transfer equipment.
5. The installation of exhaust hood for the commercial range is not yet installed.
|
||||
Miscellaneous/Other
Comment Only
06/17/2020
All RI inspections approved
|
||||
Electrical Final Inspection | Passed | 8/6/2020 (12:30 - 2:30) | 8/6/2020 (PM) | 08/06/2020 |
Corrections:
Miscellaneous/Other
Comment Only
08/06/2020
All corrections have been made.
Final inspection approved.
|