Summary

PREL201906807
Electrical
Finaled
RICHFIELD/BLOOMINGTON CREDIT UNION
Other
2-Story Addition at RBCU Bank
06/24/2019
07/26/2019
10/20/2020

Locations

Permits

Permit Number: PREL201906807

Electrical
Finaled
07/26/2019
10/20/2020

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 9/17/2019 (8:00 - 10:00) 9/17/2019 (AM) 09/17/2019
Corrections:


Miscellaneous/Other
Comment Only
09/17/2019
Wall RI 2nd level partial east half- ok

Electrical Rough-in Inspection Partial Pass 9/24/2019 (8:00 - 10:00) 9/24/2019 (AM) 09/24/2019
Corrections:


Miscellaneous/Other
Comment Only
09/24/2019
Second level walls- ok Roof top RI- ok

Electrical Rough-in Inspection Partial Pass 10/2/2019 (10:00 - 12:00) 10/2/2019 (AM) 10/02/2019
Corrections:


Miscellaneous/Other
Comment Only
10/02/2019
Partial 1st floor wall RI- ok

Electrical Rough-in Inspection Partial Pass 10/9/2019 (8:00 - 10:00) 10/9/2019 (AM) 10/09/2019
Corrections:


Miscellaneous/Other
Comment Only
10/09/2019
1st floor wall RI- ok

Electrical Rough-in Inspection Partial Pass 12/10/2019 (8:00 - 10:00) 12/10/2019 (AM) 12/10/2019
Corrections:


Miscellaneous/Other
Carried Forward
12/10/2019
Attach fixtures to grid

Miscellaneous/Other
Carried Forward
12/10/2019
Remove temp wiring in ceiling.

Miscellaneous/Other
Comment Only
12/10/2019
Ok to cover will verify during finals. Need minimum 1 hour for finals

Electrical Final Inspection Partial Pass 12/19/2019 (8:00 - 10:00) 12/19/2019 (AM) 12/19/2019
Corrections:


Miscellaneous/Other
Carried Forward
12/19/2019
Available fault currents marked on equipment far exceed ratings of the equipment.

Miscellaneous/Other
Carried Forward
12/19/2019
Secondary side of transformer has no OCP for panel board. per NEC 408.36B

Miscellaneous/Other
Carried Forward
12/19/2019
Verify generator feeder sizing and grounding / bonding. Transfer switches are 4 pole and would require generator to have GEC installed.

Miscellaneous/Other
Carried Forward
12/19/2019
GEC for transformer installed in EMT needs to be bonded at each end or be installed in non-ferrous metallic raceway.

Miscellaneous/Other
Comment Only
12/19/2019
RTU on rooftop rated at 35ka SCCR. - ok

Miscellaneous/Other
Comment Only
12/19/2019
Walk through in addition area only for outlets and lighting - ok Generator test for LS transfer at 10 seconds and lighting came to full brightness at normal loss.

Electrical Rough-in Inspection Partial Pass 12/31/2019 (10:00 - 12:00) 12/31/2019 (AM) 12/31/2019
Corrections:


Miscellaneous/Other
Comment Only
12/31/2019
Office wall RI phase 2 , 1st and 2nd floors.

Electrical Rough-in Inspection Partial Pass 1/15/2020 (12:30 - 2:30) 1/15/2020 (PM) 01/15/2020
Corrections:


Miscellaneous/Other
Comment Only
01/15/2020
Wall RI for bathrooms and two offices spaces.

Electrical Rough-in Inspection Partial Pass 1/30/2020 (2:30 - 3:30) 1/30/2020 (PM) 01/30/2020
Corrections:


Miscellaneous/Other
Comment Only
01/30/2020
2 nd floor wall RI- ok

Lighting Inspection Sign Passed 02/17/2020
RBCU Parking lot lighting 9550 Lyndale
Electrical Rough-in Inspection Partial Pass 3/5/2020 (12:30 - 2:30) 3/5/2020 (PM) 03/05/2020
Corrections:


Miscellaneous/Other
Comment Only
03/05/2020
2nd floor above ceiling - ok

Electrical Rough-in Inspection Partial Pass 3/18/2020 (8:00 - 10:00) 3/18/2020 (AM) 03/18/2020
Corrections:


Miscellaneous/Other
Comment Only
03/18/2020
1st level Above ceiling- ok Service panel disconnect- ok

Electrical Final Inspection Passed 4/8/2020 (10:00 - 12:00) 4/8/2020 (AM) 04/08/2020
Corrections:


Miscellaneous/Other
Comment Only
04/08/2020
Final for bank- ok GFCI- ok

Electrical Final Inspection Passed 04/23/2020
Corrections:


Miscellaneous/Other
Outstanding
12/19/2019
Available fault currents marked on equipment far exceed ratings of the equipment.

Miscellaneous/Other
Outstanding
12/19/2019
Secondary side of transformer has no OCP for panel board. per NEC 408.36B

Miscellaneous/Other
Outstanding
12/19/2019
Verify generator feeder sizing and grounding / bonding. Transfer switches are 4 pole and would require generator to have GEC installed.

Miscellaneous/Other
Outstanding
12/19/2019
GEC for transformer installed in EMT needs to be bonded at each end or be installed in non-ferrous metallic raceway.

Electrical Rough-in Inspection Passed 04/23/2020
Corrections:


Miscellaneous/Other
Outstanding
12/10/2019
Attach fixtures to grid

Miscellaneous/Other
Outstanding
12/10/2019
Remove temp wiring in ceiling.