PREL201907689
There are no deposits or bonds for this permit application.
| Inspection | Outcome | Requested | Scheduled | Date Complete |
|---|---|---|---|---|
| Electrical Final Inspection | Partial Pass | 10/16/2019 (10:00 - 12:00) | 10/16/2019 (AM) | 10/16/2019 |
|
Corrections:
Miscellaneous/Other
Comment Only
10/16/2019
Locker room area- ok
Front Entry wall RI- ok
|
||||
|
Miscellaneous/Other
Carried Forward
10/16/2019
Locker room 7- GFCI not functioning
Ref room - GFCI not functioning
|
||||
|
Miscellaneous/Other
Carried Forward
10/16/2019
HVAC control boxes need to be supported.
|
||||
| Electrical Rough-in Inspection | Partial Pass | 10/28/2019 (12:30 - 2:30) | 10/28/2019 (PM) | 10/28/2019 |
|
Corrections:
Miscellaneous/Other
Resolved
10/28/2019
Locker room 7- GFCI not functioning
Ref room - GFCI not functioning
|
||||
|
Miscellaneous/Other
Carried Forward
10/28/2019
HVAC control boxes need to be supported.
|
||||
|
Miscellaneous/Other
Comment Only
10/28/2019
Entry ceiling- ok
|
||||
| Electrical Rough-in Inspection | Partial Pass | 1/15/2020 (10:00 - 12:00) | 1/15/2020 (AM) | 01/15/2020 |
|
Corrections:
Miscellaneous/Other
Resolved
01/15/2020
HVAC control boxes need to be supported.
|
||||
|
Miscellaneous/Other
Carried Forward
01/15/2020
Need bonding jumper minimum #8.
Panel schedule needed.
Send pictures when complete.
|
||||
| Electrical Rough-in Inspection | Passed | 05/19/2020 | ||
|
Corrections:
Miscellaneous/Other
Resolved
05/19/2020
Need bonding jumper minimum #8.
Panel schedule needed.
Send pictures when complete.
|
||||
| Electrical Final Inspection | Passed | 05/19/2020 | ||
|
Corrections:
Miscellaneous/Other
Comment Only
05/19/2020
All issues resolved final- ok
|
||||