Permit Application Status

PREL201908772


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL201908772
Electrical
Permit(s) Issued
VORANDESOTO LLC
Alteration/Repair/Replace
Tenant improvement Beyond Family Chiropractic
08/01/2019
08/02/2019
09/07/2021

Locations

Permits

Permit Number: PREL201908772

Electrical
Expired
08/02/2019
09/07/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Pending
Corrections:


Miscellaneous/Other
Outstanding
10/10/2019
No sign installed. Sign installation will require separate permit.

Miscellaneous/Other
Outstanding
10/10/2019
Verify if RTU is existing or new install. 50a OCP with number 10 wires, verify nameplate requirements.

Electrical Rough-in Inspection Failed 8/6/2019 (12:30 - 2:30) 8/6/2019 (PM) 08/06/2019
Corrections:


Miscellaneous/Other
Carried Forward
08/06/2019
Patient care areas require redundant grounding systems per NEC 517. Adjustment rooms and possibly consult rooms.

Electrical Rough-in Inspection Partial Pass 8/8/2019 (10:00 - 12:00) 8/8/2019 (AM) 08/08/2019
Corrections:


Miscellaneous/Other
Resolved
08/08/2019
Patient care areas require redundant grounding systems per NEC 517. Adjustment rooms and possibly consult rooms.

Miscellaneous/Other
Comment Only
08/08/2019
EMT installed for patient areas wall RI- ok

Electrical Rough-in Inspection Passed w/ Conditions 10/1/2019 (2:30 - 3:30) 10/1/2019 (PM) 10/01/2019
Corrections:


Miscellaneous/Other
Comment Only
10/01/2019
Above ceiling - ok Couple of Jboxes left to splice and cover.

Miscellaneous/Other
Comment Only
10/01/2019
Left note for General permits required for all FA work and Temp control work.

Miscellaneous/Other
Comment Only
10/01/2019
Verifying listing and wiring requirements of Xray machine

Electrical Final Inspection Failed 10/7/2019 (12:30 - 2:30) 10/7/2019 (PM) 10/07/2019
Corrections:


Miscellaneous/Other
Carried Forward
10/07/2019
In the procedure rooms the isolated ground receptacles are not allowed. per NEC 517.16A Receptacles need to be hospital grade with the green dot.

Miscellaneous/Other
Carried Forward
10/07/2019
Metal boxes must be connected to EGC in all areas including procedure rooms and be connected to the receptacles.

Miscellaneous/Other
Carried Forward
10/07/2019
EGC in panel and disconnect to Xray machine have doubled up wires on lugs. Lugs do not appear to be rated for 2 wires.

Miscellaneous/Other
Carried Forward
10/07/2019
No sign installed

Miscellaneous/Other
Carried Forward
10/07/2019
Verify if RTU is existing or new install.

Electrical Final Inspection Partial Pass 10/10/2019 (8:00 - 10:00) 10/10/2019 (AM) 10/10/2019
Corrections:


Miscellaneous/Other
Resolved
10/10/2019
In the procedure rooms the isolated ground receptacles are not allowed. per NEC 517.16A Receptacles need to be hospital grade with the green dot.

Miscellaneous/Other
Resolved
10/10/2019
Metal boxes must be connected to EGC in all areas including procedure rooms and be connected to the receptacles.

Miscellaneous/Other
Resolved
10/10/2019
EGC in panel and disconnect to Xray machine have doubled up wires on lugs. Lugs do not appear to be rated for 2 wires.

Miscellaneous/Other
Carried Forward
10/10/2019
No sign installed. Sign installation will require separate permit.

Miscellaneous/Other
Carried Forward
10/10/2019
Verify if RTU is existing or new install. 50a OCP with number 10 wires, verify nameplate requirements.