PREL201909550
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 9/23/2019 (8:00 - 10:00) | 9/23/2019 (AM) | 09/23/2019 |
Corrections:
Miscellaneous/Other
Comment Only
09/23/2019
Inspector is coordinating FA inspections for this contractor - with inspections for Medina Electric under Permit # 201900814. at each inspection FA cabling is viewed/inspected and individual sign off card at each unit is signed.
|
||||
Miscellaneous/Other
Comment Only
09/23/2019
Met contractor on site for - walk thru.
FA cable has been inspected at previous site inspections.
Areas approved to date for FA cable installations:
Units, corridors and stairwells: 6th floor 603-621, 5th floor 503-521,4th floor # 403-421, 3rd floor #304-321, 2nd floor #203-223. SW stairwell and center stairwell for FA Cable install OK.
|
||||
Electrical Rough-in Inspection | Partial Pass | 11/14/2019 | ||
Corrections:
Miscellaneous/Other
Comment Only
11/14/2019
RI Ok at units south central 4th, 5th, 6th floors-
#601, 602, 668- 676. 501, 502, 568-576, 401,402, 468- 476
|
||||
Electrical Rough-in Inspection | Passed | 04/09/2020 | ||
Corrections:
Miscellaneous/Other
Comment Only
04/09/2020
All Rough- In inspections were performed in conjunction with RI inspections performed under permit # 201900814.
All RI inspections approved.
|
||||
Electrical Final Inspection | Passed | 04/09/2020 | ||
Corrections:
Miscellaneous/Other
Comment Only
04/09/2020
Fire alarm cable installations are complete. Testing by Bloomington Fire Inspections.
|