Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Pending
Corrections:


Miscellaneous/Other
Outstanding
10/22/2019
Sign letters have listing labels. This is not a section label. As such- the power supply is field installed and not part of the sign listing. See NEC 600.24 - the Class 2 power supply shall be listed for use with electric signs. The power supply installed is a recognized component only. Call for re-inspection.

Electrical Rough-in Inspection Partial Pass 9/11/2019 (10:00 - 12:00) 9/11/2019 (AM) 09/11/2019
Corrections:


Miscellaneous/Other
Comment Only
09/11/2019
Wall RI OK

Electrical Rough-in Inspection Partial Pass 9/17/2019 (2:30 - 3:30) 9/17/2019 (PM) 09/17/2019
Corrections:


Miscellaneous/Other
Comment Only
09/17/2019
Front of house- hard lid ceiling RI OK

Electrical Rough-in Inspection Partial Pass 9/20/2019 (8:00 - 10:00) 9/20/2019 (AM) 09/20/2019
Corrections:


Miscellaneous/Other
Comment Only
09/20/2019
Above ceiling RI OK at front of store

Electrical Rough-in Inspection Passed 10/08/2019
Corrections:


Miscellaneous/Other
Comment Only
10/08/2019
South 148. Meet contractor onsite to discuss listing and labeling requirements.

Electrical Final Inspection Failed 10/22/2019 (2:30 - 3:30) 10/22/2019 (PM) 10/22/2019
Corrections:


Miscellaneous/Other
Comment Only
10/22/2019
Final- partial pass only. 20 days to repair correction for sign power supply.

Miscellaneous/Other
Carried Forward
10/22/2019
Sign letters have listing labels. This is not a section label. As such- the power supply is field installed and not part of the sign listing. See NEC 600.24 - the Class 2 power supply shall be listed for use with electric signs. The power supply installed is a recognized component only. Call for re-inspection.