Summary

PREL201911178
Electrical
Finaled
THE BEDROOM INC
Other
New ground up building for HOM Furniture (HOM, Gabberts, Dock 86)
09/23/2019
10/14/2019
11/14/2020
05/18/2020

Locations

Permits

Permit Number: PREL201911178

Electrical
Finaled

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 10/15/2019 (12:30 - 2:30) 10/15/2019 (PM) 10/15/2019
Miscellaneous/Other
Comment Only
10/15/2019
UG south basement- ok

Electrical Rough-in Inspection Partial Pass 10/28/2019 (10:00 - 12:00) 10/28/2019 (AM) 10/28/2019
Miscellaneous/Other
Comment Only
10/28/2019
Gabberts UG- ok

Electrical Rough-in Inspection Partial Pass 11/15/2019 (10:00 - 12:00) 11/15/2019 (AM) 11/15/2019
Miscellaneous/Other
Comment Only
11/15/2019
LL wall RI- ok

Miscellaneous/Other
Outstanding
11/15/2019
Service bonding jumper needs 750 sizing. GEC need to be installed.

Electrical Rough-in Inspection Partial Pass 12/20/2019 (8:00 - 10:00) 12/20/2019 (AM) 12/20/2019
Miscellaneous/Other
Carried Forward
12/20/2019
Still need performance testing of service GFPE. per NEC 230.95(C)

Miscellaneous/Other
Carried Forward
12/20/2019
Service needs to be labeled with Available fault currents and dates.

Miscellaneous/Other
Comment Only
12/20/2019
Wall RI for partial 1st level, west of 1st elevator.

Miscellaneous/Other
Comment Only
12/20/2019
No UG inspection for lot lights.

Electrical Rough-in Inspection Partial Pass 1/10/2020 (12:30 - 2:30) 1/10/2020 (PM) 01/10/2020
Miscellaneous/Other
Carried Forward
01/10/2020
Still need performance testing of service GFPE. per NEC 230.95(C)

Miscellaneous/Other
Carried Forward
01/10/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment.

Miscellaneous/Other
Comment Only
01/10/2020
First floor wall RI.- ok

Miscellaneous/Other
Carried Forward
01/10/2020
Floor outlet needed in meeting rooms NEC 210.71

Electrical Rough-in Inspection Partial Pass 1/24/2020 (8:00 - 10:00) 1/24/2020 (AM) 01/24/2020
Miscellaneous/Other
Carried Forward
01/24/2020
Still need performance testing of service GFPE. per NEC 230.95(C)

Miscellaneous/Other
Carried Forward
01/24/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment.

Miscellaneous/Other
Carried Forward
01/24/2020
Floor outlet needed in meeting rooms NEC 210.71

Miscellaneous/Other
Carried Forward
01/24/2020
Need Arc Energy reduction documentation per NEC 240.87

Miscellaneous/Other
Comment Only
01/24/2020
Wall Ri central area 2nd floor - ok

Miscellaneous/Other
Carried Forward
01/24/2020
Need to verify sign listings being installed and large sign along highway.

Electrical Rough-in Inspection Partial Pass 1/31/2020 (10:00 - 12:00) 1/31/2020 (AM) 01/31/2020
Miscellaneous/Other
Carried Forward
01/31/2020
Still need performance testing of service GFPE. per NEC 230.95(C)

Miscellaneous/Other
Carried Forward
01/31/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment.

Miscellaneous/Other
Carried Forward
01/31/2020
Floor outlet needed in meeting rooms NEC 210.71

Miscellaneous/Other
Carried Forward
01/31/2020
Need Arc Energy reduction documentation per NEC 240.87

Miscellaneous/Other
Carried Forward
01/31/2020
Need to verify sign listings being installed and large sign along highway.

Miscellaneous/Other
Comment Only
01/31/2020
Wall RI 2nd floor - ok

Miscellaneous/Other
Carried Forward
01/31/2020
Verify sizing of supply side bonding jumpers and feeder EGC.

Electrical Rough-in Inspection Partial Pass 2/5/2020 (8:00 - 10:00) 2/5/2020 (AM) 02/05/2020
Miscellaneous/Other
Carried Forward
02/05/2020
Still need performance testing of service GFPE. per NEC 230.95(C)

Miscellaneous/Other
Carried Forward
02/05/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment.

Miscellaneous/Other
Carried Forward
02/05/2020
Floor outlet needed in meeting rooms NEC 210.71

Miscellaneous/Other
Carried Forward
02/05/2020
Need Arc Energy reduction documentation per NEC 240.87

Miscellaneous/Other
Resolved
02/05/2020
Need to verify sign listings being installed and large sign along highway.

Miscellaneous/Other
Carried Forward
02/05/2020
Verify sizing of supply side bonding jumpers and feeder EGC.

Miscellaneous/Other
Comment Only
02/05/2020
Met sign contractor onsite. Checked listings and labels.- ok

Electrical Rough-in Inspection Partial Pass 2/21/2020 (12:30 - 2:30) 2/21/2020 (PM) 02/21/2020
Miscellaneous/Other
Carried Forward
02/21/2020
Still need performance testing of service GFPE. per NEC 230.95(C)

Miscellaneous/Other
Carried Forward
02/21/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment, Elevators.

Miscellaneous/Other
Carried Forward
02/21/2020
Floor outlet needed in meeting rooms NEC 210.71

Miscellaneous/Other
Carried Forward
02/21/2020
Need Arc Energy reduction documentation per NEC 240.87

Miscellaneous/Other
Carried Forward
02/21/2020
Verify sizing of supply side bonding jumpers and feeder EGC. Sign feeder sizing OCP protection oversized for wire size.

Miscellaneous/Other
Carried Forward
02/21/2020
HP- 2 panel has 400a feeder, panel rated at 225a.

Miscellaneous/Other
Carried Forward
02/21/2020

Electrical Rough-in Inspection Partial Pass 2/26/2020 (10:00 - 12:00) 2/26/2020 (AM) 02/26/2020
Miscellaneous/Other
Carried Forward
02/26/2020
Still need performance testing of service GFPE. per NEC 230.95(C)

Miscellaneous/Other
Carried Forward
02/26/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment, Elevators.

Miscellaneous/Other
Carried Forward
02/26/2020
Floor outlet needed in meeting rooms NEC 210.71

Miscellaneous/Other
Carried Forward
02/26/2020
Need Arc Energy reduction documentation per NEC 240.87

Miscellaneous/Other
Carried Forward
02/26/2020
Verify sizing of supply side bonding jumpers and feeder EGC. Sign feeder sizing OCP protection oversized for wire size.

Miscellaneous/Other
Carried Forward
02/26/2020
HP- 2 panel has 400a feeder, panel rated at 225a.

Miscellaneous/Other
Carried Forward
02/26/2020

Electrical Final Inspection Partial Pass 4/3/2020 (12:30 - 2:30) 4/3/2020 (PM) 04/03/2020
Miscellaneous/Other
Comment Only
04/03/2020
Lower level final - ok

Miscellaneous/Other
Carried Forward
04/07/2020
Verify temp wiring removed. View list of RI corrections for future finals.

Lighting Inspection Sign Passed 04/05/2020
Electrical Final Inspection Failed 4/7/2020 (12:30 - 2:30) 4/7/2020 (PM) 04/07/2020
Miscellaneous/Other
Outstanding
04/07/2020
Light poles require grounding

Miscellaneous/Other
Outstanding
04/07/2020
RTU’s verify all EGC have pulled to units. Verify all OCP in disconnects and panel are - ok Available fault current’s needed at unit, all units are 5K rated.

Miscellaneous/Other
Outstanding
04/07/2020
Temp wiring needs to be removed from ceilings.

Electrical Rough-in Inspection Partial Pass 4/20/2020 (8:00 - 10:00) 4/20/2020 (AM) 04/20/2020
Miscellaneous/Other
Carried Forward
04/20/2020
Still need performance testing of service GFPE. per NEC 230.95(C)

Miscellaneous/Other
Carried Forward
04/20/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment, Elevators.

Miscellaneous/Other
Resolved
04/20/2020
Floor outlet needed in meeting rooms NEC 210.71

Miscellaneous/Other
Resolved
04/20/2020
Need Arc Energy reduction documentation per NEC 240.87

Miscellaneous/Other
Resolved
04/20/2020
Verify sizing of supply side bonding jumpers and feeder EGC. Sign feeder sizing OCP protection oversized for wire size.

Miscellaneous/Other
Resolved
04/20/2020
HP- 2 panel has 400a feeder, panel rated at 225a.

Miscellaneous/Other
Comment Only
04/20/2020

Electrical Final Inspection Partial Pass 4/28/2020 (8:00 - 10:00) 4/28/2020 (AM) 04/29/2020
Miscellaneous/Other
Resolved
04/29/2020
Verify temp wiring removed. View list of RI corrections for future finals.

Miscellaneous/Other
Carried Forward
04/29/2020
Available fault current on HP-M, HP-LL, and HP-1 appear to be higher than equipment ratings.

Miscellaneous/Other
Carried Forward
04/29/2020
Still need RTU numbers or letters for equipment ratings

Electrical Rough-in Inspection Passed 05/05/2020
Miscellaneous/Other
Outstanding
04/20/2020
Still need performance testing of service GFPE. per NEC 230.95(C)

Miscellaneous/Other
Outstanding
04/20/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment, Elevators.

Progress Inspection Passed 05/05/2020
Miscellaneous/Other
Comment Only
05/05/2020
Follow conversation for fault current calculations

Electrical Final Inspection Passed 5/18/2020 (12:30 - 2:30) 5/18/2020 (PM) 05/18/2020
Miscellaneous/Other
Resolved
05/18/2020
Available fault current on HP-M, HP-LL, and HP-1 appear to be higher than equipment ratings. Contractor verified CB ratings- ok

Miscellaneous/Other
Resolved
05/18/2020
Still need RTU numbers or letters for equipment ratings