Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Rough-in Inspection | Partial Pass | 10/15/2019 (12:30 - 2:30) | 10/15/2019 (PM) | 10/15/2019 |
Corrections:
Miscellaneous/Other
Comment Only
10/15/2019
UG south basement- ok
|
||||
Electrical Rough-in Inspection | Partial Pass | 10/28/2019 (10:00 - 12:00) | 10/28/2019 (AM) | 10/28/2019 |
Corrections:
Miscellaneous/Other
Comment Only
10/28/2019
Gabberts UG- ok
|
||||
Electrical Rough-in Inspection | Partial Pass | 11/15/2019 (10:00 - 12:00) | 11/15/2019 (AM) | 11/15/2019 |
Corrections:
Miscellaneous/Other
Comment Only
11/15/2019
LL wall RI- ok
|
||||
Miscellaneous/Other
Outstanding
11/15/2019
Service bonding jumper needs 750 sizing.
GEC need to be installed.
|
||||
Electrical Rough-in Inspection | Partial Pass | 12/20/2019 (8:00 - 10:00) | 12/20/2019 (AM) | 12/20/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
12/20/2019
Still need performance testing of service GFPE. per NEC 230.95(C)
|
||||
Miscellaneous/Other
Carried Forward
12/20/2019
Service needs to be labeled with Available fault currents and dates.
|
||||
Miscellaneous/Other
Comment Only
12/20/2019
Wall RI for partial 1st level, west of 1st elevator.
|
||||
Miscellaneous/Other
Comment Only
12/20/2019
No UG inspection for lot lights.
|
||||
Electrical Rough-in Inspection | Partial Pass | 1/10/2020 (12:30 - 2:30) | 1/10/2020 (PM) | 01/10/2020 |
Corrections:
Miscellaneous/Other
Carried Forward
01/10/2020
Still need performance testing of service GFPE. per NEC 230.95(C)
|
||||
Miscellaneous/Other
Carried Forward
01/10/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment.
|
||||
Miscellaneous/Other
Comment Only
01/10/2020
First floor wall RI.- ok
|
||||
Miscellaneous/Other
Carried Forward
01/10/2020
Floor outlet needed in meeting rooms NEC 210.71
|
||||
Electrical Rough-in Inspection | Partial Pass | 1/24/2020 (8:00 - 10:00) | 1/24/2020 (AM) | 01/24/2020 |
Corrections:
Miscellaneous/Other
Carried Forward
01/24/2020
Still need performance testing of service GFPE. per NEC 230.95(C)
|
||||
Miscellaneous/Other
Carried Forward
01/24/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment.
|
||||
Miscellaneous/Other
Carried Forward
01/24/2020
Floor outlet needed in meeting rooms NEC 210.71
|
||||
Miscellaneous/Other
Carried Forward
01/24/2020
Need Arc Energy reduction documentation per NEC 240.87
|
||||
Miscellaneous/Other
Comment Only
01/24/2020
Wall Ri central area 2nd floor - ok
|
||||
Miscellaneous/Other
Carried Forward
01/24/2020
Need to verify sign listings being installed and large sign along highway.
|
||||
Electrical Rough-in Inspection | Partial Pass | 1/31/2020 (10:00 - 12:00) | 1/31/2020 (AM) | 01/31/2020 |
Corrections:
Miscellaneous/Other
Carried Forward
01/31/2020
Still need performance testing of service GFPE. per NEC 230.95(C)
|
||||
Miscellaneous/Other
Carried Forward
01/31/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment.
|
||||
Miscellaneous/Other
Carried Forward
01/31/2020
Floor outlet needed in meeting rooms NEC 210.71
|
||||
Miscellaneous/Other
Carried Forward
01/31/2020
Need Arc Energy reduction documentation per NEC 240.87
|
||||
Miscellaneous/Other
Carried Forward
01/31/2020
Need to verify sign listings being installed and large sign along highway.
|
||||
Miscellaneous/Other
Comment Only
01/31/2020
Wall RI 2nd floor - ok
|
||||
Miscellaneous/Other
Carried Forward
01/31/2020
Verify sizing of supply side bonding jumpers and feeder EGC.
|
||||
Electrical Rough-in Inspection | Partial Pass | 2/5/2020 (8:00 - 10:00) | 2/5/2020 (AM) | 02/05/2020 |
Corrections:
Miscellaneous/Other
Carried Forward
02/05/2020
Still need performance testing of service GFPE. per NEC 230.95(C)
|
||||
Miscellaneous/Other
Carried Forward
02/05/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment.
|
||||
Miscellaneous/Other
Carried Forward
02/05/2020
Floor outlet needed in meeting rooms NEC 210.71
|
||||
Miscellaneous/Other
Carried Forward
02/05/2020
Need Arc Energy reduction documentation per NEC 240.87
|
||||
Miscellaneous/Other
Resolved
02/05/2020
Need to verify sign listings being installed and large sign along highway.
|
||||
Miscellaneous/Other
Carried Forward
02/05/2020
Verify sizing of supply side bonding jumpers and feeder EGC.
|
||||
Miscellaneous/Other
Comment Only
02/05/2020
Met sign contractor onsite. Checked listings and labels.- ok
|
||||
Electrical Rough-in Inspection | Partial Pass | 2/21/2020 (12:30 - 2:30) | 2/21/2020 (PM) | 02/21/2020 |
Corrections:
Miscellaneous/Other
Carried Forward
02/21/2020
Still need performance testing of service GFPE. per NEC 230.95(C)
|
||||
Miscellaneous/Other
Carried Forward
02/21/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment, Elevators.
|
||||
Miscellaneous/Other
Carried Forward
02/21/2020
Floor outlet needed in meeting rooms NEC 210.71
|
||||
Miscellaneous/Other
Carried Forward
02/21/2020
Need Arc Energy reduction documentation per NEC 240.87
|
||||
Miscellaneous/Other
Carried Forward
02/21/2020
Verify sizing of supply side bonding jumpers and feeder EGC. Sign feeder sizing OCP protection oversized for wire size.
|
||||
Miscellaneous/Other
Carried Forward
02/21/2020
HP- 2 panel has 400a feeder, panel rated at 225a.
|
||||
Miscellaneous/Other
Carried Forward
02/21/2020
|
||||
Electrical Rough-in Inspection | Partial Pass | 2/26/2020 (10:00 - 12:00) | 2/26/2020 (AM) | 02/26/2020 |
Corrections:
Miscellaneous/Other
Carried Forward
02/26/2020
Still need performance testing of service GFPE. per NEC 230.95(C)
|
||||
Miscellaneous/Other
Carried Forward
02/26/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment, Elevators.
|
||||
Miscellaneous/Other
Carried Forward
02/26/2020
Floor outlet needed in meeting rooms NEC 210.71
|
||||
Miscellaneous/Other
Carried Forward
02/26/2020
Need Arc Energy reduction documentation per NEC 240.87
|
||||
Miscellaneous/Other
Carried Forward
02/26/2020
Verify sizing of supply side bonding jumpers and feeder EGC. Sign feeder sizing OCP protection oversized for wire size.
|
||||
Miscellaneous/Other
Carried Forward
02/26/2020
HP- 2 panel has 400a feeder, panel rated at 225a.
|
||||
Miscellaneous/Other
Carried Forward
02/26/2020
|
||||
Electrical Final Inspection | Partial Pass | 4/3/2020 (12:30 - 2:30) | 4/3/2020 (PM) | 04/03/2020 |
Corrections:
Miscellaneous/Other
Comment Only
04/03/2020
Lower level final - ok
|
||||
Miscellaneous/Other
Carried Forward
04/07/2020
Verify temp wiring removed. View list of RI corrections for future finals.
|
||||
Lighting Inspection Sign | Passed | 04/05/2020 | ||
HOM Furniture sign 7800 Dupont | ||||
Electrical Final Inspection | Failed | 4/7/2020 (12:30 - 2:30) | 4/7/2020 (PM) | 04/07/2020 |
Corrections:
Miscellaneous/Other
Outstanding
04/07/2020
Light poles require grounding
|
||||
Miscellaneous/Other
Outstanding
04/07/2020
RTU’s verify all EGC have pulled to units.
Verify all OCP in disconnects and panel are - ok
Available fault current’s needed at unit, all units are 5K rated.
|
||||
Miscellaneous/Other
Outstanding
04/07/2020
Temp wiring needs to be removed from ceilings.
|
||||
Electrical Rough-in Inspection | Partial Pass | 4/20/2020 (8:00 - 10:00) | 4/20/2020 (AM) | 04/20/2020 |
Corrections:
Miscellaneous/Other
Carried Forward
04/20/2020
Still need performance testing of service GFPE. per NEC 230.95(C)
|
||||
Miscellaneous/Other
Carried Forward
04/20/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment, Elevators.
|
||||
Miscellaneous/Other
Resolved
04/20/2020
Floor outlet needed in meeting rooms NEC 210.71
|
||||
Miscellaneous/Other
Resolved
04/20/2020
Need Arc Energy reduction documentation per NEC 240.87
|
||||
Miscellaneous/Other
Resolved
04/20/2020
Verify sizing of supply side bonding jumpers and feeder EGC. Sign feeder sizing OCP protection oversized for wire size.
|
||||
Miscellaneous/Other
Resolved
04/20/2020
HP- 2 panel has 400a feeder, panel rated at 225a.
|
||||
Miscellaneous/Other
Comment Only
04/20/2020
|
||||
Electrical Final Inspection | Partial Pass | 4/28/2020 (8:00 - 10:00) | 4/28/2020 (AM) | 04/29/2020 |
Corrections:
Miscellaneous/Other
Resolved
04/29/2020
Verify temp wiring removed. View list of RI corrections for future finals.
|
||||
Miscellaneous/Other
Carried Forward
04/29/2020
Available fault current on HP-M, HP-LL, and HP-1 appear to be higher than equipment ratings.
|
||||
Miscellaneous/Other
Carried Forward
04/29/2020
Still need RTU numbers or letters for equipment ratings
|
||||
Electrical Rough-in Inspection | Passed | 05/05/2020 | ||
Corrections:
Miscellaneous/Other
Outstanding
04/20/2020
Still need performance testing of service GFPE. per NEC 230.95(C)
|
||||
Miscellaneous/Other
Outstanding
04/20/2020
Service needs to be labeled with Available fault currents and dates. Also need fault currents for all feeders panel boards, HVAC equipment, Elevators.
|
||||
Progress Inspection | Passed | 05/05/2020 | ||
Corrections:
Miscellaneous/Other
Comment Only
05/05/2020
Follow conversation for fault current calculations
|
||||
Electrical Final Inspection | Passed | 5/18/2020 (12:30 - 2:30) | 5/18/2020 (PM) | 05/18/2020 |
Corrections:
Miscellaneous/Other
Resolved
05/18/2020
Available fault current on HP-M, HP-LL, and HP-1 appear to be higher than equipment ratings.
Contractor verified CB ratings- ok
|
||||
Miscellaneous/Other
Resolved
05/18/2020
Still need RTU numbers or letters for equipment ratings
|