Electrical Final Inspection | Failed | 10/29/2019 (10:00 - 12:00) | 10/29/2019 (AM) | 10/29/2019 |
Corrections:
Miscellaneous/Other
Carried Forward
10/29/2019
Circuit breaker location needs to be full opposite of feeder location per 705.12B(2)3b
|
||||
Miscellaneous/Other
Carried Forward
10/29/2019
Panel requires appropriate labeling per 705
|
||||
Miscellaneous/Other
Carried Forward
10/29/2019
Rapid shutdown label required for disconnect.
|
||||
Miscellaneous/Other
Carried Forward
10/29/2019
Neutral for production meter is bonded to meter can. Neutral must be isolated, EGC cannot be used for this purpose.
|
||||
Electrical Final Inspection | Passed | 11/13/2019 (3:30 - 4:00) | 11/13/2019 (PM) | 11/14/2019 |
Corrections:
Miscellaneous/Other
Resolved
11/14/2019
Circuit breaker location needs to be full opposite of feeder location per 705.12B(2)3b
|
||||
Miscellaneous/Other
Resolved
11/14/2019
Panel requires appropriate labeling per 705
|
||||
Miscellaneous/Other
Resolved
11/14/2019
Rapid shutdown label required for disconnect.
|
||||
Miscellaneous/Other
Resolved
11/14/2019
Neutral for production meter is bonded to meter can. Neutral must be isolated, EGC cannot be used for this purpose.
|
||||
Miscellaneous/Other
Comment Only
11/14/2019
Neutral jumper removed from meter socket. No neutral present for meter. Xcel will determine if needed for meter usage. neutral cannot be reinstalled to EGC in meter can.
Xcel contacted.
|