PREL201914743
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Final Inspection | Partial Pass | 12/12/2019 (12:30 - 2:30) | 12/12/2019 (PM) | 12/12/2019 |
Released to Xcel 35 AMP - 480 Volt 3 phase- transformer located in service cabinet as part of the equipment tmiller 12/17/2019 8:34 AM | ||||
Corrections:
Miscellaneous/Other
Comment Only
12/12/2019
Service OK to release to Xcel-
35 AMP main- 480 volt 3 phase.
|
||||
Provide and label available fault current at service location
Carried Forward
12/12/2019
Provide and label available fault current at service location.
Install Arc flash warning label.
|
||||
Electrical Final Inspection | Failed | 1/7/2020 (10:00 - 12:00) | 1/7/2020 (AM) | 01/07/2020 |
Corrections:
Provide and label available fault current at service location
Carried Forward
01/07/2020
Provide and label available fault current at service location.
Install Arc flash warning label.
|
||||
Miscellaneous/Other
Carried Forward
01/07/2020
Available fault current label has completely faded and is not readable.
Labels must withstand weather conditions subjected to. Relabel and call for reinspection
|
||||
Electrical Final Inspection | Passed | 1/15/2020 (12:30 - 2:30) | 1/15/2020 (PM) | 01/15/2020 |
Tim out sick- Move to 1-14-20.NelsonThorpe Sarah 01/13/2020 7:28 AM | ||||
Corrections:
Provide and label available fault current at service location
Resolved
01/15/2020
Provide and label available fault current at service location.
Install Arc flash warning label.
|
||||
Miscellaneous/Other
Resolved
01/15/2020
Available fault current label has completely faded and is not readable.
Labels must withstand weather conditions subjected to. Relabel and call for reinspection
|