Summary

PREL201914743
Electrical
Finaled
IKEA PROPERTY INC
Other
Cell tower - new service and 2 circuits on pole
12/09/2019
12/09/2019
07/13/2020
01/15/2020

Locations

Permits

Permit Number: PREL201914743

Electrical
Finaled
12/09/2019
07/13/2020

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Partial Pass 12/12/2019 (12:30 - 2:30) 12/12/2019 (PM) 12/12/2019
Released to Xcel 35 AMP - 480 Volt 3 phase- transformer located in service cabinet as part of the equipment tmiller 12/17/2019 8:34 AM
Corrections:


Miscellaneous/Other
Comment Only
12/12/2019
Service OK to release to Xcel- 35 AMP main- 480 volt 3 phase.

Provide and label available fault current at service location
Carried Forward
12/12/2019
Provide and label available fault current at service location. Install Arc flash warning label.

Electrical Final Inspection Failed 1/7/2020 (10:00 - 12:00) 1/7/2020 (AM) 01/07/2020
Corrections:


Provide and label available fault current at service location
Carried Forward
01/07/2020
Provide and label available fault current at service location. Install Arc flash warning label.

Miscellaneous/Other
Carried Forward
01/07/2020
Available fault current label has completely faded and is not readable. Labels must withstand weather conditions subjected to. Relabel and call for reinspection

Electrical Final Inspection Passed 1/15/2020 (12:30 - 2:30) 1/15/2020 (PM) 01/15/2020
Tim out sick- Move to 1-14-20.NelsonThorpe Sarah 01/13/2020 7:28 AM
Corrections:


Provide and label available fault current at service location
Resolved
01/15/2020
Provide and label available fault current at service location. Install Arc flash warning label.

Miscellaneous/Other
Resolved
01/15/2020
Available fault current label has completely faded and is not readable. Labels must withstand weather conditions subjected to. Relabel and call for reinspection