Summary

PREL202000957
Electrical
Finaled
RWIC OFFICE PARTNERSHIP
Alteration/Repair/Replace
Remodel for tenant build out; install new fixtures, wire new receptacles, one floor box Choices Therapy
01/31/2020
02/03/2020
09/13/2020
03/17/2020

Locations

Permits

Permit Number: PREL202000957

Electrical
Finaled
02/03/2020
09/13/2020

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 2/19/2020 (8:00 - 10:00) 2/19/2020 (AM) 02/19/2020
Corrections:


Miscellaneous/Other
Comment Only
02/19/2020
Misc. wall RI- ok No card onsite

Miscellaneous/Other
Carried Forward
02/19/2020
Temp.Control and Fire Alarm permits needed for above ceiling.

Electrical Rough-in Inspection Passed 3/3/2020 (12:30 - 2:30) 3/3/2020 (PM) 03/04/2020
Corrections:


Miscellaneous/Other
Outstanding
02/19/2020
Temp.Control and Fire Alarm permits needed for above ceiling. Caltex doing stat work and FA permit pulled from Electric fire and Security 202002038

Miscellaneous/Other
Comment Only
03/04/2020
Above ceiling- ok

Electrical Final Inspection Passed w/ Conditions 3/17/2020 (8:00 - 10:00) 3/17/2020 (AM) 03/17/2020
Corrections:


Miscellaneous/Other
Comment Only
03/17/2020
GFCI possibly behind fridge. Outlet in meeting room no power.