PREL202001023
There are no deposits or bonds for this permit application.
Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Final Inspection | Pending | |||
Electrical Final Inspection | Partial Pass | 3/19/2020 (8:00 - 10:00) | 3/19/2020 (AM) | 03/20/2020 |
Released to Xcel 200 AMP OH COMM- 120/240 volt single phase Temp power for construction tmiller 03/20/2020 8:41 AM | ||||
Corrections:
Miscellaneous/Other
Comment Only
03/20/2020
Met contractor on site-
Verbal to install main bond at service.
Verbal install knock out seal.
Verbal to install additional ground rod for service & for separate building or structure at construction trailer.
Service OK to release to Xcel - 200 AMP 120/240 single phase. Temp power for construction site.
|