PO 36594 FURNISH & INSTALL 142 FIXTURES, 2 EXIT/EMERGENCY SIGNS/LIGHTS, 28 OCCUPANCY SENSORS, 2 SWITCHES, 116 RECEPTACLES, 14 PHONE/DATA OPENINGS, 2 ELECTRICAL PANELS, WIRE 1 30 GALLON WATER & HVAC, DISCONNECT WIRING FOR CONSTRUCTION.
04/15/2020
04/15/2020
02/06/2021
08/10/2020

Locations

Permits

Permit Number: PREL202003481

Electrical
Finaled
04/15/2020
02/06/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Progress Inspection Partial Pass 4/29/2020 (8:00 - 10:00) 4/29/2020 (AM) 04/29/2020
Corrections:


Miscellaneous/Other
Comment Only
04/29/2020
Site meet only

Electrical Rough-in Inspection Partial Pass 5/8/2020 (12:30 - 2:30) 5/8/2020 (PM) 05/08/2020
Corrections:


Miscellaneous/Other
Comment Only
05/08/2020
Wall RI- ok Still need above ceiling, spoke with job sup about FA and temp control permits.

Above Ceiling Inspection Partial Pass 5/26/2020 (12:30 - 2:30) 5/26/2020 (PM) 05/26/2020
Corrections:


Miscellaneous/Other
Carried Forward
05/26/2020
Hard lid ceiling RI, hall and entrance 6 access panels needed in entry

Above Ceiling Inspection Passed 7/2/2020 (8:00 - 10:00) 7/2/2020 (AM) 07/02/2020
Corrections:


Miscellaneous/Other
Outstanding
05/26/2020
Hard lid ceiling RI, hall and entrance 6 access panels needed in entry

Miscellaneous/Other
Comment Only
07/02/2020
Above ceiling RI OK for power & light. Spoke to job superintendent- fire alarm cable and temperature control work to be inspected

Electrical Final Inspection Partial Pass 7/22/2020 (10:00 - 12:00) 7/22/2020 (AM) 07/22/2020
Carter Contact 651-226-6589 [Vandewege\, Meredith 2020-07-20T11:00:11-05:00] [Vandewege\, Meredith 2020-07-20T11:00:15-05:00]
Corrections:


Miscellaneous/Other
Carried Forward
07/22/2020
Verify size of EGC in parallel 400a feeder to 480v panel.

Miscellaneous/Other
Carried Forward
07/22/2020
OCP to Aaon unit undersized needs to be max 110a minimum 101a

Miscellaneous/Other
Comment Only
07/22/2020
Room finals and GFCI- ok Temp OC, ok spoke to building inspector.

Electrical Final Inspection Passed 8/10/2020 (2:30 - 3:30) 8/10/2020 (PM) 08/10/2020
Corrections:


Miscellaneous/Other
Resolved
08/10/2020
Verify size of EGC in parallel 400a feeder to 480v panel.

Miscellaneous/Other
Resolved
08/10/2020
OCP to Aaon unit undersized needs to be max 110a minimum 101a