Permit Application Status

PREL202008207


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202008207
Electrical
Finaled
GKII NORTHLAND CENTER LLC
Alteration/Repair/Replace
New tenant buildout.
07/29/2020
08/10/2020
05/16/2021
11/17/2020

Locations

Permits

Permit Number: PREL202008207

Electrical
Finaled
08/10/2020
05/16/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Rough-in Inspection Partial Pass 8/12/2020 (12:30 - 2:30) 8/12/2020 (PM) 08/12/2020
Corrections:


Miscellaneous/Other
Comment Only
08/12/2020
Wall RI- ok

Electrical Rough-in Inspection Partial Pass 9/1/2020 (12:30 - 2:30) 9/1/2020 (PM) 09/01/2020
Corrections:


Miscellaneous/Other
Comment Only
09/01/2020
Partial above ceiling- ok

Electrical Rough-in Inspection Partial Pass 9/15/2020 (8:00 - 10:00) 9/15/2020 (AM) 09/15/2020
Corrections:


Miscellaneous/Other
Carried Forward
09/15/2020
Cord connected condensate pump in ceiling needs to be removed.

Miscellaneous/Other
Carried Forward
09/15/2020
LV still requires support in areas.

Electrical Rough-in Inspection Passed 11/16/2020 (12:30 - 2:30) 11/16/2020 (PM) 11/17/2020
Corrections:


Miscellaneous/Other
Outstanding
09/15/2020
Cord connected condensate pump in ceiling needs to be removed.

Miscellaneous/Other
Outstanding
09/15/2020
LV still requires support in areas.

Electrical Final Inspection Passed w/ Conditions 11/17/2020
Corrections:


Miscellaneous/Other
Outstanding
11/17/2020
Mothers room required GFCI protection within 6’ of sink.

Miscellaneous/Other
Comment Only
11/17/2020
Final - ok Outstanding issues need to be completed.