Summary

PREL202010291
Electrical
Finaled
BLMGTN SCHOOL DIST #271
Other
Install a 400 kWDC / 300 kWAC ballasted rooftop solar array
09/09/2020
09/24/2020
11/10/2021
05/14/2021

Locations

Permits

Permit Number: PREL202010291

Electrical
Finaled
09/24/2020
11/10/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Partial Pass 4/30/2021 (10:00 - 12:00) 4/30/2021 (AM) 04/30/2021
Corrections:


Miscellaneous/Other
Carried Forward
04/30/2021
Main sub CB plug needs to be reduced to meet the requirements of 705.

Miscellaneous/Other
Carried Forward
04/30/2021
Verify wiring not on roof under array support as necessary

Miscellaneous/Other
Carried Forward
04/30/2021
Proper plaques required.

Electrical Rough-in Inspection Passed 4/30/2021 (10:00 - 12:00) 4/30/2021 (AM) 04/30/2021
Corrections:


Miscellaneous/Other
Comment Only
04/30/2021
Met contractor on-site.

Electrical Final Inspection Passed 5/14/2021 (10:00 - 12:00) 5/14/2021 (AM) 05/14/2021
Corrections:


Miscellaneous/Other
Resolved
05/14/2021
Main sub CB plug needs to be reduced to meet the requirements of 705.

Miscellaneous/Other
Resolved
05/14/2021
Verify wiring not on roof under array support as necessary

Miscellaneous/Other
Resolved
05/14/2021
Proper plaques required.

Miscellaneous/Other
Comment Only
05/14/2021
Issues resolved. Xcel form completed for contractor.