Inspection | Outcome | Requested | Scheduled | Date Complete |
---|---|---|---|---|
Electrical Final Inspection | Pending | |||
Corrections:
Miscellaneous/Other
Outstanding
12/07/2020
Verify listing and labeling of channel letters. Ground level view only.
Inspector note: Power supply enclosure bears a listing mark from MET Labs-
however the numeration of the section label indicates that the supply is section
1 of 9. This doesn't correspond with the number of channel letters.
|
||||
Miscellaneous/Other
Outstanding
12/07/2020
Once NRTL listing and labeling are confirmed- or not: may require investigation into the listing of sign drivers.
|
||||
Miscellaneous/Other
Outstanding
12/07/2020
The secondary side installation and wiring from the driver(s) - is NOT plenum rated. The installation was evidently performed by the sign contractor. It is not yet known if the sign contractor is licensed by MNDLI as either a technology systems contractor or as an electrical contractor.
Once the listing issue is resolved- the remedy for the non-plenum rated cable is required to be performed by a licensed contractor with permit and re-inspection.
|
||||
Electrical Final Inspection | Failed | 12/7/2020 (AM) | 12/07/2020 | |
Corrections:
Miscellaneous/Other
Carried Forward
12/07/2020
Verify listing and labeling of channel letters. Ground level view only.
Inspector note: Power supply enclosure bears a listing mark from MET Labs-
however the numeration of the section label indicates that the supply is section
1 of 9. This doesn't correspond with the number of channel letters.
|
||||
Miscellaneous/Other
Carried Forward
12/07/2020
Once NRTL listing and labeling are confirmed- or not: may require investigation into the listing of sign drivers.
|
||||
Miscellaneous/Other
Carried Forward
12/07/2020
The secondary side installation and wiring from the driver(s) - is NOT plenum rated. The installation was evidently performed by the sign contractor. It is not yet known if the sign contractor is licensed by MNDLI as either a technology systems contractor or as an electrical contractor.
Once the listing issue is resolved- the remedy for the non-plenum rated cable is required to be performed by a licensed contractor with permit and re-inspection.
|
||||
Lighting Inspection | Passed | 12/09/2020 | ||
SFM wall sign 300 NITS - west wall |