Permit Application Status

PREL202010621


You will only be able to view fees or view conditions if you are a contact on the permit application.

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary

PREL202010621
Electrical
Expired
GKII NORTHLAND CENTER LLC
Alteration/Repair/Replace
Sign power
09/15/2020
09/16/2020
06/07/2021

Locations

Permits

Permit Number: PREL202010621

Electrical
Expired
09/16/2020
06/07/2021

Deposits & Bonds

There are no deposits or bonds for this permit application.

Inspections

Inspection Outcome Requested Scheduled Date Complete
Electrical Final Inspection Pending
Corrections:


Miscellaneous/Other
Outstanding
12/07/2020
Verify listing and labeling of channel letters. Ground level view only. Inspector note: Power supply enclosure bears a listing mark from MET Labs- however the numeration of the section label indicates that the supply is section 1 of 9. This doesn't correspond with the number of channel letters.

Miscellaneous/Other
Outstanding
12/07/2020
Once NRTL listing and labeling are confirmed- or not: may require investigation into the listing of sign drivers.

Miscellaneous/Other
Outstanding
12/07/2020
The secondary side installation and wiring from the driver(s) - is NOT plenum rated. The installation was evidently performed by the sign contractor. It is not yet known if the sign contractor is licensed by MNDLI as either a technology systems contractor or as an electrical contractor. Once the listing issue is resolved- the remedy for the non-plenum rated cable is required to be performed by a licensed contractor with permit and re-inspection.

Electrical Final Inspection Failed 12/7/2020 (AM) 12/07/2020
Corrections:


Miscellaneous/Other
Carried Forward
12/07/2020
Verify listing and labeling of channel letters. Ground level view only. Inspector note: Power supply enclosure bears a listing mark from MET Labs- however the numeration of the section label indicates that the supply is section 1 of 9. This doesn't correspond with the number of channel letters.

Miscellaneous/Other
Carried Forward
12/07/2020
Once NRTL listing and labeling are confirmed- or not: may require investigation into the listing of sign drivers.

Miscellaneous/Other
Carried Forward
12/07/2020
The secondary side installation and wiring from the driver(s) - is NOT plenum rated. The installation was evidently performed by the sign contractor. It is not yet known if the sign contractor is licensed by MNDLI as either a technology systems contractor or as an electrical contractor. Once the listing issue is resolved- the remedy for the non-plenum rated cable is required to be performed by a licensed contractor with permit and re-inspection.

Lighting Inspection Passed 12/09/2020
SFM wall sign 300 NITS - west wall